Contractor level parameters
The cylinder hysteresis regulates the start and stop points for
cylinderheating.ThehighertheON/OFFtemperaturedifferential,
the higher the cylinder temperature uctuation around the set
cylindertemperature.
Example: Setcylindertemperature60°C
Cylinderhysteresis5K
Cylinderheatingcommencesat55°Candendsat60°C.
Cylinder hysteresis
Parameter HG15
HG15
5
Factorysetting:5K
Settingrange:1to30K
Individual setting: ______
No. Explanation
12 Bypasspumpforreturntemperatureraising
OutputA1iscontrolledifthereturntemperatureislower
thantheselectedreturntemperatureraisingvalue
(parameterHG32).
Important: Input E1 must, in any case, be
programmed to setting 11 or if an external
burner block input E1
(HG13 = 8) has been programmed.
13 DHWcirculationpump
OutputA1iscontrolledfor5minutesafterapushbuttonhas
beenactivated(pulseinputE1).
Important: In any case, input E1 must be
programmed to setting 6.
14 OutputA1ON
OutputA1iscontrolledifinputE1isclosed
(externalburnerdemand).
Important: In any case, input E1 must be
programmed to setting 10.