Aftercompletingthecylinder heating(thecylinderhasreached
the set temperature), the cylinder primary pump willrun on up
to the maximum set run-on time. The cylinder primary pump
willswitchOFFprematurelyif,duringtherun-ontime,theboiler
watertemperaturehasfallentoadifferentialbetweenboilerand
cylinderwatertemperature of5K,topreventtheboilercooling
downtooseverely.
Cylinder primary pump
run-on time
Parameter HG19
HG19
3
Factorysetting:3min
Settingrange:0to10min
Individual setting: ______
Cylinderheatingcommencesassoonasthecylindertemperature
sensor demands heat. The heating circuit pump would be
constantlyswitchedOFF,iftheboilerwasundersized,thecylinder
wasscaled-uporifDHWwasconstantlydrawnoffduringDHW
priority mode. The accommodation cools down severely.An
option enables a max. cylinder heating time to be specied to
limitthiseffect.Thecontrolunitrevertstoheatingmode,whenthe
setcylinderheatingtimehasexpiredandcyclesintheselected
rhythmbetweenheatingandcylinderheatingmode,irrespective
ofwhetherthecylinderhasreached itsset temperatureornot.
Thisfunctionremainsenabledeveninparallelmode(parameter
A10setto1).Itisonlydisabledifitissetto0.
Set this parameter to 0 in heating systems with a high DHW
consumption,e.g.hotels,sportsfacilities,etc.
Max. DHW cylinder
heating time
Parameter HG20
HG20
2
Factorysetting:2h
Settingrange:0to5h
Individual setting: ______
Contractor level parameters