No. Items Description
13 Low Oil Pressure When the oil pressure of genset is less than threshold and Enabled Low Oil Pressure
Stop Inhibited or Input Low Oil Pressure Stop Inhibited is active, controller will send
warning alarm signal and it will be displayed in LCD.
14 Input Warn When external input is active, controller will send warning alarm signal and it will be dis‐
played in LCD.
15 Failed To Charge When Failed To Charge input is active, controller will send warning alarm signal and it
will be displayed in LCD.
16 Over Power If over power detection is enabled, when the controller detects that the over power value
(power is positive) has exceeded the pre-set value and the action select “Warn”, it will
initiate a warning alarm.
17 ECU Warn If an error message is received from ECU via J1939, it will initiate a warning alarm.
4.1.3 Shutdown Alarms
When controller detects shutdown alarm, it will send signal to open
breaker and shuts down generator.
No.
Items Description
2 High Temp. Shutdown When the temperature of water/cylinder is higher than set threshold, controller will send
a stop alarm signal and it will be displayed on the LCD.
3 Low Oil Pressure Shutdown When oil pressure is lower than threshold, controller will send a stop alarm signal and it
will be displayed on the LCD.
4 Over Speed Shutdown When genset speed is higher than set threshold, controller will send a stop alarm signal
and it will be displayed on the LCD.
5 Under Speed Shutdown When genset speed is lower than set threshold, controller will send a stop alarm signal
and it will be displayed on the LCD.
6 Loss Of Speed Signal Shutdown When rotate speed is 0 and delay is not 0, controller will send a stop alarm signal and it
will be displayed on the LCD.
7 Genset Over Voltage Shutdown When genset voltage is higher than threshold, controller will send a stop alarm signal
and it will be displayed on the LCD.
8 Genset Under Voltage Shutdown When genset voltage is under set threshold, controller will send a stop alarm signal and
it will be displayed on the LCD.
9 Genset Over Current Shutdown When genset current is higher than set threshold and delay is not 0, it will send a stop
alarm signal and it will be displayed on the LCD.
10 Failed To Start Within set start times, if failed to start, controller will send a stop alarm signal and it will
be displayed on the LCD.
11 Over Freq. Shutdown When genset frequency is higher than set threshold, controller will send a stop alarm
signal and it will be displayed on the LCD.
12 Under Freq. Shutdown When genset frequency is lower than set threshold, controller will send a stop alarm
signal and it will be displayed on the LCD.
13 Genset Failed When genset frequency is 0, controller will send a stop alarm signal and it will be dis‐
played on the LCD.
14 Low Fuel Level When fuel level low input is active, controller will send a stop alarm signal and it will be
displayed on the LCD.
15 Low Coolant Level When genset coolant level low input is active, controller will send a stop alarm signal
and it will be displayed on the LCD.
16 Temp. Sensor Open When sensor hasn’t connected to corresponding port, controller will send shutdown
alarm signal and it will be displayed on the LCD.
17 Oil Sensor Open When sensor hasn’t connected to corresponding port, controller will send shutdown
alarm signal and it will be displayed on the LCD.