8 Commissioning and Test Procedure
Commissioning should be performed when the fire control panel is not in an alarm/fault
condition. Note: No personnel should be in the risk area until the fire system is fully isolated.
Six Monthly Test Procedure:
1. Isolate the control panel (see 7.2 Isolate Function) and disconnect the
any installed FirePro aerosol generators. This will generate a fault on the
fire control panel.
2. Connect a FP-08800 Test Module to the “Discharge” output to the panel
(marked yellow). Turn off the Isolate function.
3. Control Panel and components
- Clean and remove dirt, grease or foreign material. Replace any parts
that appear damaged or are painted.
- Check all indicators are in normal position.
4. FirePro Aerosol Generators
- Inspect FirePro generators to ensure they are in good condition.
- Check mounting brackets are in good condition and secure.
- Check Dust Covers are in good condition replace as necessary.
- Check FirePro Units are pointing at predetermined aiming points.
5. Electrical Actuation system
- Check Manual Actuators are secure, clean, undamaged.
- Check that anti-tamper seals/pull pins are in place and secure.
- Check Detection system: wiring, connection and supports are in intact, not damaged
and in correct position.
6. Labels Check manual release, system warning and instruction labels are securely in place,
visible and legible.
7. Test the fault monitoring system by disconnecting and reconnecting all connected detection
devices and the siren strobe circuit one at a time. Ensure the “Fault” LED indicator
illuminates and the internal sounder is heard each time a circuit is disconnected.
8. Discharge Testing from Control Panel
- Perform a manual discharge test by pressing and holding both mode switches on the
panel continuously for 5 seconds.
- Following activation, ensure the Test Module has operated.
- Isolate the panel to silence alarm. Panel should now display a fault.
- Reset Test Module. Panel should no longer be in fault condition.
- Turn off the Isolate function.