1) Pre-Commissioning (before site)
Gather site information
Obtain copy of:
ASPIRE IDP
Site plans
Commissioning Report
Start to fill in:
Commissioning forms
Other required regulatory forms
Gather needed tools
Programmer (laptop with VSC and USB cable)
Material for acceptable smoke test
Optional: digital manometer (if sample hole pressure is required to be measured)
Wide Bore Networks: Max range 3kpa
Narrow Bore Networks: 0.20kpa at the end of the recommended length of microbore tube
2) Pre-Commissioning (at site)
Check cables
Properly terminated maintaining correct polarity
Reversed polarity may cause damage to the device
VESDAnet wiring (closed or open-ended loop)
Record the serial number from each VESDA device
- Detectors, displays, and remote relay modules
VESDA-E SeriesLegacy Detectors