38
R
MC
S
T
400/200V
M
VS−616G5
3
IM
THRX
OFF
ON
MC
SA
1
2
MC
TRX
TRX
20 18
SA
SA
THRX
MC
P
B
12
3
4
Overload Relay Trip Contact
(Thermal Protector Contact:
230VAC, 1A or less)
Level
Detection
Braking Unit
Braking Resistor
Unit (Option)
Cooling Fan
r (
1
)
Voltage
Selection
Motor
MCCB
3−Phase
Power Supply
380 to 460 V
50/60 Hz
Overload Relay Trip Contact
of Braking Resistor Unit
Fault
Contact
400
( 2 400)
Cooling Fin Overheat Contact
(Thermoswitch Contact:
250VAC, 1A or less
30VDC, 1A or less)
U (T1)
V (T2)
W (T3)
L1 (R)
L2 (S)
L3 (T)
0
0
460/440/415/
400/380V
Use sequencer to break
power supply side on over-
load relay trip contact of
braking resistor unit.
Failure to observe this can
result in a fire.
∗∗
Where is “E” or “V”.
When using the braking resistor unit, set constant L3−04 to
“0” (stall prevention selection during decel is disabled).
If it is not changed, the inverter may not stop within set decel time.
Ground (200V Class : 100Ω or less
400V Class : 10Ω or less)
Fig. 18 For Models CIMR-G54055 to -G54160 (400 V Class 55 to 160 kW)