VS−616G5
THRX
OFF
ON
MC
SA
12
MC
TRX
TRX
18
20
SA
SA
THRX
P
3
4
B
1
2
MC
≈
≈
U (T1)
V(T2)
W(T3)
Overload Relay Trip Contact
(Thermal Protector Contact:
230VAC, 1A or less)
Braking Resistor
Unit (Option)
Motor
Cooling Fin Overheat Contact
(Thermoswitch Contact:
250VAC, 1A or less
30VDC, 1A or less)
Level
Detection
Braking Unit
Cooling Fan
r(
1)
MCCB
L1 (R)
L2 (S)
L3 (T)
Overload Relay Trip Contact
of Braking Resistor Unit
Fault
Contact
(
2
)
3−Phase
Power Supply
200 to 230 V
50/60 Hz
0
0
Ground (200V Class : 100Ω or less
400V Class : 10Ω or less)
∗∗
Where is “E” or “V”.
When using the braking resistor unit, set constant L3−04 to
“0” (stall prevention selection during decel is disabled).
If it is not changed, the inverter may not stop within set decel time.
Use sequencer to break
power supply side on over-
load relay trip contact of
braking resistor unit.
Failure to observe this can
result in a fire.