Standard Specifications
22
YASKAWA
YASKAWA AC Drive
CH700
Catalog
KAEP C710617 24
*
200 V Class
Catalog Code CH7
0
A
2
003
005
008
011
014
018
025
033
047
060
075
088
115
145
180
215
283
346
415
Max. Applicable
kW
Motor Capacity
*
1
0.4
0.75
1.5
2.2
3
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
Input
Rated Input
A
Current
3.6
4.8
8.9
12.7
17
20.7
30
40.3
58.2
78.4
96
82
111
136
164
200
271
324
394
Output
Rated Output
A
Current
3.2
5
8
11
14
17.5
25
33
47
60
75
88
115
145
180
215
283
346
415
Overload
Tolerance
150
% of rated output current for
60
s
Note
:
Derating may be required for applications that start and stop frequently.
Carrier
Frequency
Derating the output current enables a maximum of
15
kHz to be set.
(
Derating the output current is not necessary up to
8
kHz.
)
Derating the output current enables a
maximum of
10
kHz to be set.
(
Derating the output current is not
necessary up to
5
kHz.
)
Max. Output
Voltage
Three
-
phase
200
to
240
V
Note
:
The maximum output voltage is proportional to the input voltage.
Max. Output
Frequency
590 Hz
The frequencies that can be set vary depending on the control mode used.
Measures
for
Harmonics
DC Reactor
External options
Built
-
in
Braking
Function
Braking
Transistor
Built
-
in
External options
EMC
filter
EMC filter
EN
61800
-
3
, C
2
/C
3
Internal
(
factory option
)
Power
Rated Voltage /
Rated Frequency
Three
-
phase AC power supply
200
V to
240
V
50
/
60
Hz
DC power supply
270
V to
340
V
Allowable
Voltage
Fluctuation
15
% to
10
%
Allowable
Frequency
Fluctuation
±
5
%
Power
kVA
Supply
*
2
1.5
2.0
3.7
5.3
7.1
8.6
12.5
16.8
24.2
32.6
39.9
34.1
46.1
56.5
68.2
83.1
113
135
164
1
:
For the most appropriate selection, contact your Yaskawa or nearest sales representative.
*
2
:
Rated input capacity is calculated with a power line voltage of
240
V.