12 Drive Control, Duty Modes, and Programming
58 YASKAWA TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide
No.
(Hex.)
Name Description
E2-01
(030E)
Motor Rated Current (FLA) Sets the motor rated current in amps.
E2-11
(0318)
Motor Rated Power Sets the motor rated power in 0.01 kW increments. (1 HP = 0.746 kW)
H1-01 - H1-10
(0438, 0439, 0400 -
0407)
Terminal Sx Function Select Sets the functions for MFDI terminals S1 to S10.
H2-01
(040B)
Term M1-M2 Function Selection Sets the function for MFDO terminal M1-M2.
H2-02
(040C)
Term M3-M4 Function Selection Sets the function for MFDO terminal M3-M4.
H2-03
(040D)
Term M5-M6 Function Selection Sets the function for MFDO terminal M5-M6.
H2-04
(040E)
Term P1-C1 Function Selection Sets the function for MFDO terminal P1-C1.
H2-05
(040F)
Term P2-C2 Function Selection Sets the function for MFDO terminal P2-C2.
H3-01
(0410)
Terminal A1 Signal Level Select Sets the input signal level for MFAI terminal A1.
0: 0-10V (Lower Limit at 0), 1: -10 to +10V (Bipolar Reference)
H3-02
(0434)
Terminal A1 Function Selection Sets the function for MFAI terminal A1.
H3-03
(0411)
RUN
Terminal A1 Gain Setting Sets the gain of the analog signal input to MFAI terminal A1.
H3-04
(0412)
RUN
Terminal A1 Bias Setting Sets the bias of the analog signal input to MFAI terminal A1.
H3-05
(0413)
Terminal A3 Signal Level Select Sets the input signal level for MFAI terminal A3.
0: 0-10V (Lower Limit at 0), 1: -10 to +10V (Bipolar Reference)
H3-06
(0414)
Terminal A3 Function Selection Sets the function for MFAI terminal A3.
H3-07
(0415)
RUN
Terminal A3 Gain Setting Sets the gain of the analog signal input to MFAI terminal A3.
H3-08
(0416)
RUN
Terminal A3 Bias Setting Sets the bias of the analog signal input to MFAI terminal A3.
H3-09
(0417)
Terminal A2 Signal Level Select Sets the input signal level for MFAI terminal A2.
0: 0-10V (Lower Limit at 0), 1: -10 to +10V (Bipolar Reference), 2: 4 to 20 mA, 3: 0 to 20 mA
H3-10
(0418)
Terminal A2 Function Selection Sets the function for MFAI terminal A2.
H3-11
(0419)
RUN
Terminal A2 Gain Setting Sets the gain of the analog signal input to MFAI terminal A2.
H3-12
(041A)
RUN
Terminal A2 Bias Setting Sets the bias of the analog signal input to MFAI terminal A2.
H3-13
(041B)
Analog Input FilterTime Constant Sets the time constant for primary delay filters on MFAI terminals.
H3-14
(041C)
Analog Input Terminal Enable Sel Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select = Analog Terminal Enable Selection]
is ON.
1: Terminal A1 only, 2: Terminal A2 only, 3: Terminals A1 and A2, 4: Terminal A3 only, 5: Terminals A1 and A3,
6: Terminals A2 and A3, 7: Terminals A1, A2, and A3
H4-01
(041D)
Terminal FM Analog Output
Select
Sets the monitor number to send from MFAO terminal FM.
H4-02
(041E)
RUN
Terminal FM Analog Output Gain Sets the gain of the Ux-xx monitor signal set in H4-01 [terminals FM Monitor Selection].
H4-03
(041F)
RUN
Terminal FM Analog Output Bias Sets the bias of the Ux-xx monitor signal set in H4-01 [Terminal FM Analog Output Select].