15 European Standards
92 YASKAWA TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide
2. Wire the drive and motor.
3. Ground the wire shielding on the drive side and motor side.
A - Drive
B - 10 m (32.8 ft) maximum
C - Motor
D - Metal conduit
E - Grounding wire
Figure 15.4 Wiring the Drive and Motor
Note:
Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
The maximum wiring length between the drive and motor is 10 m (32.8 ft). Keep the wire as short as possible.
Keep the grounding wire as short as possible.
4. Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications and local safety standards.
A - Braided shield cable
B - Metal plate
C - Cable clamp (conductive)
Figure 15.5 Ground the Shield