15 European Standards
YASKAWA TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide 99
A - Grounding surface (Remove any paint or
sealant.)
B - Enclosure panel
C - Metal plate
D - Drive Series
E - Ground the shield.
F - Motor
G - Motor cable (Braided shield cable: max. 10 m
(32.8 ft.))
H - Cable clamp
I - Grounding wire
J - EMC noise filter
Figure 15.17 EMC Noise Filter and Drive Installation Procedure
5. Connect the DC reactor to decrease harmonic distortion. Refer to DC Reactor on page 101 to select a DC
reactor.
Note:
• To maintain compliance with IEC/EN 61000-3-2 on drive models 2003, 2005, 4002, 4003, install a DC reactor.
• The main circuit terminal block for the drive, and the terminal blocks for the DC reactor come in different shapes. The drive
has a European style terminal block, and the DC reactor has a round terminal block. Correctly prepare the ends of the
wiring.
Ground Wiring
WARNING
Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you
touch the internal components of an energized drive, it can cause serious injury or death.
EN