7 Troubleshooting
YASKAWA ELECTRIC TOBP C730600 49A V1000 Option MECHATROLINK-II Installation Manual 25
LED Operator Display Fault Name
E5
SI-T Watchdog Timer Error
The watchdog has timed out.
Cause Possible Solution
Data has not been received from the
PLC, triggering the watchdog timer.
Execute DISCONNECT or ALM_CLR, then issue a CONNECT
command or SYNC_SET command and proceed to phase 3.
LED Operator Display Fault Name
EF0
External Fault Input from MECHATROLINK-II Option
The alarm function for an external device has been triggered.
Cause Possible Solution
An external fault is being sent from
the master controller (PLC).
Remove the cause of the external fault.
Reset the external fault input from the PLC device.
Problem with the PLC program
Check the program used by the PLC and make the appropriate
corrections.
LED Operator Display Fault Name
oFA00
MECHATROLINK-II Option Fault
MECHATROLINK-II Option is not properly connected.
Cause Possible Solution
Non-compatible option connected to
the drive
Connect an option that is compatible with the drive.
LED Operator Display Fault Name
oFA01
MECHATROLINK-II Option Fault
MECHATROLINK-II Option is not properly connected.
Cause Possible Solution
Problem with the connectors between
the drive and MECHATROLINK-II
Option
Turn the power off and check the connectors between the drive and
MECHATROLINK-II Option.