7 Troubleshooting
YASKAWA ELECTRIC TOBP C730600 49A V1000 Option MECHATROLINK-II Installation Manual 27
Minor Faults and Alarms
LED Operator Display Minor Fault Name
AEr
Station Address Error
MECHATROLINK-II Option is set to an address outside the allowable
setting range.
Cause Possible Solution
Minor Fault
(H2- = 10)
Address outside the specified address
range
Set F6-20 to an address within the specified range. YES
LED Operator Display Minor Fault Name
CALL
Serial Communication Transmission Error
Communication has not yet been established.
Cause Possible Solution
Minor Fault
(H2- = 10)
Communication wiring is faulty, there
is a short circuit, or something is not
connected properly.
Check for wiring errors.
Correct the wiring.
Remove and ground shorts and reconnect loose
wires.
YES
Programming error on the master side
Check communications at start-up and correct
programming errors.
Communication circuitry is damaged.
Perform a self-diagnostics check.
Replace the drive if the fault continues to occur.