22
6 Initial Setup
Before starting communications between the Inverter and the MECHATROLINK master, set
the following constants as required.
* To run or stop through the MECHATROLINK communications, set 3 to
B1-02. To set frequency, set 3 to B1-01.
For details, refer to the Varispeed G7/F7 Series Instruction Manual
(TOE-S616-60.1, TOE-S616-55.1).
Constant
No.
Name Description Factory
Setting
B1-02
Run command
selection
0: Digital Operator
1: Control circuit terminal
2: MEMOBUS communications
3: Communications Option Card (Optional)
1
B1-01
Frequency reference
selection
0: Digital Operator
1: Voltage reference
2: MEMOBUS communications
3: Communications Option Card (Optional)
4: Pulse train reference
1