29
40 0128H
Multi-function output
selection
0: Fault
1: During run
2: Frequency agree
3: During zero speed
4: Frequency detection
(detection level or greater)
5: Frequency detection
(detection level or less)
6: During over torque detection
(N. O. contact output)
7: During over torque detection
(N. C. contact output)
8: Not used
9: Not used
10: Minor fault (during warning display)
11: During baseblock
12: Run mode
13: Inverter ready
14: During fault retry
15: During UV
16: During reverse run
17: During speed search
18: Data output through communication
187
41 0129H
Analog frequency
reference gain
Setting unit: 1%
Setting range: 0 - 255%
100% 67
42 012AH
Analog frequency
reference bias
Setting unit: 1%
Setting range: –99 ~ 99%
0% 67
43 012BH
Analog frequency
reference filter time
parameter
Setting unit: 0.01s
Setting range: 0.00 ~ 2.00s
(Note)