Appendix 4. Functions Related to Upgrade
App.4-4
TI 33K01B10-50E
Table Functions Related to Upgrade Before R5.03.00 (4/7)
Item Function
CENTUM V or
CENTUM-XL
CENTUM VP Measures
SUB output
terminal
SUB output
terminal∆PV
calculation
SUB terminal provides
the following output if an
IOP occurs:
∆PV=0or∆CPV=0
If an IOP occurs, the
function block provides
∆PV(calculationblock
provides∆CPVoutput)
even when PV value
overshooting occurs. (If
overshooting does not
occur,both∆PVand
∆CPVare0asPVvalues
do not change even if an
IOP occurs.)
When the FCS property’s
[dPV/dCPVOutputfrom
SUBBecomesZeroRight
After IOP] checkbox ON is
specied,theSUBterminal
provides∆PV=0or∆CPV
= 0 output when an IOP
occurs.
Totalizer data Data set to
totalizer value
Even if the instrument
totalizer “NO” is
specied,itispossibleto
set data to SUM values.
If the function block
totalizer“NO”isspecied,
it is not possible to set
data to SUM values.
Specifyingthe[SumValue
Entry] menu in the function
block detail builder makes
data setting to SUM values
from HIS possible.
CALCU/
CALCU-C
pulse train
input
Totalizer data
specication
with pulse train
inputs (batch
data totalizer
type)
– If the pulse train input
(batch data totalizer) is
selected with CALCU, RV
rather than CPV is used
for totalization.
IfCPVinthe[DataItemfor
Totalization] menu in the
function block detail builder
isspecied,CPVisusedfor
totalization.
PID-TP
instrument
PID-TP control
algorithm
The method of selecting control algorithms differs
between CENTUM-XL and CS or later systems, so
differential control action results in CAS mode.
In CS or later systems, only PV proportional and
derivative-typePIDcontrol(I-PD)isused(xed).A
buildersuchasaPIDblockcannotbespecied.
The[PIDcontrolalgorithms]
menu in the function
block detail builder allows
the selection of control
algorithms identical to PID
algorithms, as given below:
• ProportionalPVDerivative
Type PID Control
• PVDerivativePIDControl
• BasicTypeID
• AutomaticDetermination2
• AutomaticDetermination
Output action – Positionaltype(xed) [AuxiliaryOutputType]
menu in the function block
detail builder allows the
selection of positional or
velocity output action.
BSETU
compatible
mode
`
Starting/
restarting blocks
by sequence
table action
BSETU/7BS
Start: LOOP = AUT,
SV = 0
Suspend: LOOP = CAS
Restart: LOOP = AUT
Reset: LOOP = MAN
BSETU-2/3
Start: MODE = AUT,
SW = 1
Suspend: SW = 4
Restart: SW = 2
Reset: SW = 3
Specifying[CENTUMV/
CENTUM-XL Compatible]
in the function block detail
builder allows batch starting
or restarting depending on
the conditions with ACT.
ON descriptions on the
sequence table, or the like.
Restart during
EMST
Restart is accepted even
during EMST.
Does not restart under
ZONE8(duringEMST
or while MV values are
decreasing).
Specifying[CENTUMV/
CENTUM-XL Compatible] or
[CENTUM-XLCompatible]
in the function block detail
builder can accept restart
instructions when BSTS =
EMST (while MV values are
decreasing in an emergency
stop).
Mar. 27, 2015-00