<6. Operation>
53
IM 01C25A01-01E
6.2.2 Adjusting Zero Point for Gauge/
Absolute Pressure Transmitters
(1) When you can obtain the Low Range Value
from the actual measured value of 0%
(0 kPa, atmospheric pressure);
(2) When you cannot obtain the Low Range
Value from the actual measured value of
0%;
130–50
250–50
Actual measured value=
x100=40.0%
(=10.4mA)
6.3 Local Parameter Setting
WARNING
location.
IMPORTANT
setting.
procedure.
6.3.1 Local Parameter Setting (LPS)
Overview
is carried out.
External adjustment screw cover
F0604.ai
Figure 6.3 External Adjustment Screw
Integral indicator
Push-button
F0605.ai
Figure 6.4 Range –Setting Switch (push button)