EasyManuals Logo

YOKOGAWA DPharp EJA530E User Manual

YOKOGAWA DPharp EJA530E
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
<6. Operation>
53
IM 01C25A01-01E
6.2.2 Adjusting Zero Point for Gauge/
Absolute Pressure Transmitters
(1) When you can obtain the Low Range Value
from the actual measured value of 0%
(0 kPa, atmospheric pressure);
(2) When you cannot obtain the Low Range
Value from the actual measured value of
0%;
130–50
250–50
Actual measured value=
x100=40.0%
(=10.4mA)
6.3 Local Parameter Setting
WARNING
location.
IMPORTANT
setting.
procedure.
6.3.1 Local Parameter Setting (LPS)
Overview
is carried out.
External adjustment screw cover
F0604.ai
Figure 6.3 External Adjustment Screw
Integral indicator
Push-button
F0605.ai
Figure 6.4 Range –Setting Switch (push button)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA DPharp EJA530E and is the answer not in the manual?

YOKOGAWA DPharp EJA530E Specifications

General IconGeneral
BrandYOKOGAWA
ModelDPharp EJA530E
CategoryTransmitter
LanguageEnglish

Related product manuals