<Appendix 2 Software Download>
App.2-3
IM 12A01A02-71E 3rd Edition : Mar. 23, 2018-00
NOTE
Becarefulaboutthenoiseontheeldbuslink.Iftheeldbusisnoisy,thedownloadingmaytake
a very long time or fail.
n Download Files
Downloadleshavethefollowinglenames(withthelenameextensionof“.d”).Takecareto
choosethecorrectdownloadleforthetargetelddevice:
“594543” + device family + “_” + device type + “_” + domain name + “_” + software name +
“_”+softwarerevision+“.d”
Forexample,thenameofthedownloadleforFLXA21-PHmayhavethefollowingname:
5945430402_0402_FLXA21PH_ORIGINAL_R101.d
Referto(3)DOMAIN_HEADERinpageApp.2-8abouteachkeywordofthelename.
The device type is “0402” for FLXA21-PH, and is “0403” for FLXA21-SC.
Thesoftwarenameis“ORIGINAL”or“UPDATE.”Theformerindicatesanoriginalleandthe
latteranupdatele.Wheneverperformingadownloadtoupdatethedevicerevision,obtainthe
originalle.Ingeneral,anadditiontotheparametersorblocksrequiresadevicerevisionupdate.
n Steps after Activating a Field Device
Whenthecommunicationwithaelddevicehasrecoveredafteractivatingthedevice,check
usingthedownloadtoolthatthesoftwarerevisionoftheelddevicehasbeenupdated
accordingly. The value of SOFT_REV of the resource block indicates the software revision.
The PD tag, node address, and Sensor transducer block calibration parameters that are retained
in the nonvolatile memory inside the target device will remain unchanged after a software
download. However, after a software update which causes an addition to the block parameters or
blocks, or to the system/network management VFD parameters, some parameters may be reset
to the defaults, thus requiring parameter setup and engineering again. For details, see the table
below.
Also note that a change in the number of parameters or blocks requires the DD and capabilities
lescorrespondingtothenewsoftwarerevision.
Table 1 Actions after Software Update
Contents of Software Update Action
Does not change the number of
parameters.
Re-setup of parameters not needed.
Adds a block parameter. Setup of the added parameter needed.
Adds a block. Reengineering and setup of the added
block’s parameters needed.
Changes the number of system/network
management VFD parameters.
Reengineering needed.