Explicit Message
Datatobeaccessed Tagname
Type Number Datatype
INT16
Datatype
INT32
Datatype
FLOAT
Alarm information of I/O
channel
(Continuous channel data
area)*
0801 int[10580] ‒ ‒
• • • • • •
0810 int[10589]
0901 int[10590]
• • • • • •
0910 int[10599]
Alarm information of
computation channel
A001 int[11000] ‒ ‒
• • • • • •
A200 int[11199]
Alarm information of
communication channel
C001 int[12000] ‒ ‒
• • • • • •
C500 int[12499]
“• • •” stands for data in numerical order.
* The “continuous channel data area” is a special area that enables continuous reading by limiting
the number of channels of each module to 10.
For only the I/O channels on a GX/GP main unit or I/O channels on a GM main unit, this area
can be used to read data consecutively.
• There is no decimal place information.
Error code Meaning
0 No error
1 Skip
2 +Over
3 –Over
4 +Burnout
5 –Burnout
6 A/D error
7 Invalid data
16 Computation error
17 Communication error
5 bits 4 bits
Status information
Alarm list
0
Reserved
area
Error code
RJC error
A/D calibration
value error
0 0 0 0
Level 2
Level 3
Level 4
Higher
Lower