EasyManua.ls Logo

YOKOGAWA UM330 - Page 12

YOKOGAWA UM330
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-6
<Toc> <1. Installation>
IM 05F01D02-41E 1st Edition : May 31,2000-00
Cable Specifications and Recommended Cables
Purpose Name and Manufacturer
Power supply, grounding, relay contact outputs
600 V PVC insulated wires, JIS C 3307, 0.9 to 2.0 mm
2
Thermocouple Shielded compensating lead wires, JIS C 1610, X- - -
(See Yokogawa Electric's GS 6B1U1-E.)
RTD Shielded wires (three conductors), UL2482 (Hitachi Cable)
Other signals Shielded wires
Recommended Terminal Lugs
3.7mm
7 mm or less
3.7mm
7 mm or less
or
0.3 to 1.65 mm
2
0.8 N·m or less
Applicable wire size Tightening torque
Terminal Covers
Target Model Part Number Sales Unit
UM350 T9115YD 1
UM330 T9115YE 1

Related product manuals