EasyManua.ls Logo

YOKOGAWA UM330 - Setting Hysteresis in Alarm Setpoint

YOKOGAWA UM330
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
<Toc> <2. Initial Settings>
2-11
IM 05F01D02-41E 1st Edition : May 31,2000-00
2.5 Setting Hysteresis in Alarm Setpoint
The following operating procedure describes an example of setting a 5.0°C hysteresis level
in the alarm setpoint.
1.
Bring the operating display into view
(appears at power-on).
PV
AL1234
SET/ENT
Displays PV.
2.
Press the
SET/ENT
key for more than 3 sec-
onds to call up the menu OP.PA.
PV
AL1234
SET/ENT
Displays
menu OP.PA.
3.
Press the key once to display the
menu STUP.
PV
AL1234
SET/ENT
Displays
menu STUP.
4.
Press the
SET/ENT
key once to display the
parameter PWD.
PV
AL1234
SET/ENT
Displays
parameter
PWD.
5.
Press the
SET/ENT
key once to display the
menu FUNC.
PV
AL1234
SET/ENT
Displays
menu FUNC.
6.
Press the
SET/ENT
key several times to
display the parameter HY1 (alarm-1
hysteresis).
PV
AL1234
SET/ENT
Displays
parameter
HY1.
7.
Press the or key to display the
required setpoint.
PV
AL1234
SET/ENT
Blinks during
change.
8.
Press the
SET/ENT
key once to register the
setpoint.
PV
AL1234
SET/ENT
You can take the same steps for alarm-2
hysteresis (HY2), alarm-3 hysteresis (HY3),
and alarm-4 hysteresis (HY4) that are
displayed after this.
9.
Press the
SET/ENT
key for more than 3 sec-
onds. This returns you to the display
shown at power-on (figure below).
PV
AL1234
SET/ENT
Displays PV.

Related product manuals