5.2 How to Connect Signal Cables
The following methods for connecting signal cables are available:
Direct connection using pressure clamp terminals
Connector connection using signal cables via terminal boards
Connecting an input/output module to a terminal board
Connecting a terminal board to a field
Connection via MIL connectors
IMPORTANT
It is recommended to use twisted-pair batch shielded cables for analog inputs in order to
prevent induced noise. A pitch of 50 mm or less for the twisted-pair cables is more effec-
tive. Grounding is required for the shielding. Twisted-pair cables are recommended for
digital signals as well.
Fasten the cables securely to cable clamps, etc., so that the cables do not weigh on the
terminals.