035-16004-001-A-0202
Unitary Products Group 7
BHA
POWER
SUPPLY
COMPRES
-
SOR
OUT
-
DOOR
FAN
MOTOR
FLA
SUPPLY
AIR
BLOWE
R
MOTOR,
FLA
ELECTRIC HEAT ACCESSORY
MINIMUM
CIRCUIT
AMPAC
-
ITY
MAX.
FUSE
SIZE,
AMPS
MAX.
HACR
BREAKER
SIZE
MODEL
RLA LRA MODEL NO.
STAGE
KW
TOTAL
AMPS
036 575-3-60 4.5 32.0 0.4 1.5
2NH04501058
2NH04501558
1
1
10.0 ***
15.0 ***
9.6
14.4
19.6
25.6
20
30
20
30
042 575-3-60 5.8 44.0 0.4 1.5
2NH04501058
2NH04501558
1
1
10.0 ***
15.0 ***
9.6
14.4
21.1
27.2
25
30
25
30
048 575-3-60 5.6 44.0 0.6 1.6
2NH04501058
2NH04501558
2NH04502058
2NH04502558
1
1
2
2
10.0 ***
15.0 ***
20.0 ***
25.0 ***
9.6
14.4
19.2
24.1
21.3
27.3
33.3
39.3
25
30
35
40
25
30
35
40
060 575-3-60 6.4 50.0 0.6 2.8
2NH04501058
2NH04501558
2NH04502058
2NH04502558
1
1
2
2
10.0 ***
15.0 ***
20.0 ***
25.0 ***
9.6
14.4
19.2
24.1
23.4
29.5
35.5
41.5
25
30
40
45
25
30
40
45
= Dual element, time delay type. * = KW listed is for 240 volts, use table at top of page for 208 or 230 volts.
= Standard circuit breakers may be used in Canada and on applications ** = KW listed is for 480 volts, use table at top of page for 460 volts.
over 60 amps where the heaters are separately fused. *** = KW listed is for 600 volts, use table at top of page for 575 volts.
TABLE 5 - ELECTRICAL DATA (HEAT PUMP / ELECTRIC HEAT) (Continued)