5011492-XIM-B-0815
50 Johnson Controls Unitary Products
Simplicity SE Control Board Navigation
Components
The following components are needed to access the control
points in the Simplicity® SE control. Installation and operation
guides are located on www.upgnet.com under Product Center \
Equipment Catalog \ Commercial Products \ Zoning Systems
and Controls.
1. Local LCD on Unit Control Board.
2. Mobile Access Portal (MAP) Gateway (Portable).
Source 1 P/N S1-JC-MAP1810-OP
3. MAP Gateway Quick Start Guide P/N 24-10737-16
4. MAP Gateway Instruction P/N 24-10737-8
NOTE: For more in-depth sequence of operation of the
Simplicity® SE control please refer to LIT-12011950 on
www.upgnet.com under Product Center \ Equipment
Catalog \ Commercial Products \ Zoning Systems and
Controls.
Figure 24: Unit Control Board
Ta
ble 28: Unit Control Board Flash Codes
Flash Code Description
On Steady
Control Failure - Replace Control
Heart Beat
Normal Operation
1 Flash
Not Applicable
2 Flashes
Control waiting ASCD
1
1. These flash codes do not represent alarms.
3 Flashes
HPS1 - Compressor Lock out
5 Flashes
LPS1 - Compressor Lock out
7 Flashes
FS1 - Compressor Lock out
9 Flashes
Ignition Control Locked Out/
Ignition Control Failure / Limit Switch Trip / No
Jumper Plug in Heat Section
10 Flashes
Compressors Locked Out On Low
Outdoor Air Temperature
1
11 Flashes
Compressors Locked Out Because The
Economizer Is Using Free Cooling
1
13 Flashes
Compressor Held Off Due To Low Voltage
1
14 Flashes
EEPROM Storage Failure (Control Failure)
OFF
No Power or Control Failure
Comm Setup
Button
Last Error
Button
Test Reset
Button
Control Board
LED
Table 29: Ignition Control Board Flash Codes
Flash Code Description
Heart Beat
Normal Operation
1 Flash
Not Applicable
2 Flashes
Pressure / Centrifugal Switch Open with Inducer On
3 Flashes
Pressure / Centrifugal Switch Closed with Inducer Off
4 Flashes
Not Applicable
5 Flashes
Lock Out From Too Many Flame Losses
6 Flashes
High Temperature Switch Open (Primary or Aux.)
7 Flashes
Rollout Switch Open
8 Flashes
Flame Present With Gas Off
9 Flashes
Gas Valve Stuck Off or On
10 Flashes
Flame Sense Circuit Failure