EasyManua.ls Logo

York FCHP090 - User Manual

York FCHP090
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
GENERAL
These completely assembled indoor units include a well-
insulated cabinet, a copper tube/aluminum fin coil, throw
-
away filters, a centrifugal blower, a blower motor, an adjust
-
able V-belt drive, a blower motor contactor and a small
holding charge of an inert gas. They also include a filter-
drier, an expansion valve and a distributor that are only used
during the cooling cycle plus A check valve to provide the
proper flow of refrigerant through the coil during both the
cooling and heating cycles.
Supplemental resistance heaters, a supply air plenum, a return
air grille and a base are available as accessories for field instal
-
lation.
The units are shipped in the vertical position ready for field in
-
stallation. For horizontal installation, reverse the solid bottom
panel and the return air duct flange on the front of the unit.
REFERENCE
This instruction covers the installation of the indoor unit. For in
-
formation on the installation and operation of the matching out
-
door unit, refer to Form 035-15409-002.
Renewal Parts:
Refer to Parts Manual for complete listing of replacement
parts on this equipment.
All forms referenced in this instruction may be ordered from:
Standard Register
Toll Free Tel.: 877-318-9675
Toll Free Fax: 877-379-7920
Installer should pay particular attention to the words: NOTE,
CAUTION and WARNING. Notes
are intended to clarify or
make the installation easier. Cautions
are given to prevent
equipment damage. Warnings
are given to alert the installer
that personal injury and/or equipment damage may result if the
installation procedure is not handled properly.
INSPECTION
As soon as a unit is received, it should be inspected for possi
-
ble damage during transit. If damage is evident, the extent of
the damage should be noted on the carrier's freight bill. Asepa
-
MODELS FCHP090 & FDHP120
INSTALLATION
MANUAL
Supersedes: 515.41-N2W (194)/035-11845-000 035-11845-001-A-0304
SPLIT-SYSTEM HEAT PUMPS
INDOOR UNITS
CAUTION
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE
WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND
ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES
INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL,
AND MECHANICAL CODES.
WARNING
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION,
SERVICE OR MAINTENANCE CAN CAUSE INJURY OR
PROPERTY DAMAGE. REFER TO THIS MANUAL. FOR
ASSISTANCE OR ADDITIONAL INFORMATION, CONSULT A
QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS
SUPPLIER.
Question and Answer IconNeed help?

Do you have a question about the York FCHP090 and is the answer not in the manual?

Summary

GENERAL

REFERENCE

Covers indoor unit installation and refers to the matching outdoor unit manual.

INSTALLATION

LIMITATIONS

Specifies compliance with national and local safety codes for unit installation.

LOCATION

Details requirements for indoor unit placement within the building structure.

RIGGING AND HANDLING

Provides instructions and warnings for safely moving and handling the unit.

CLEARANCES

Outlines minimum required clearances for proper unit operation and service.

VERTICAL AND HORIZONTAL INSTALLATION

Explains conversion procedures for vertical or horizontal unit installation.

DUCT CONNECTIONS

Details design and installation of ductwork according to national and local codes.

REFRIGERANT MAINS

Discusses procedures for installing refrigerant lines to ensure a clean, dry system.

DRAIN CONNECTION

Explains the necessity of trapping the drain line and the required trap depth.

SUPPLY AIR BLOWER ADJUSTMENT

Guides on adjusting blower RPM based on CFM, accessories, and static resistance.

POWER AND CONTROL WIRING

WIRING INSTALLATION AND ROUTING

Install wiring per NEC/local codes, ground unit, and route wires through knockouts.

MOTOR ROTATION AND ELECTRIC HEAT WIRING

Check/reverse motor rotation; refer to electric heat accessory instructions.

Summary

GENERAL

REFERENCE

Covers indoor unit installation and refers to the matching outdoor unit manual.

INSTALLATION

LIMITATIONS

Specifies compliance with national and local safety codes for unit installation.

LOCATION

Details requirements for indoor unit placement within the building structure.

RIGGING AND HANDLING

Provides instructions and warnings for safely moving and handling the unit.

CLEARANCES

Outlines minimum required clearances for proper unit operation and service.

VERTICAL AND HORIZONTAL INSTALLATION

Explains conversion procedures for vertical or horizontal unit installation.

DUCT CONNECTIONS

Details design and installation of ductwork according to national and local codes.

REFRIGERANT MAINS

Discusses procedures for installing refrigerant lines to ensure a clean, dry system.

DRAIN CONNECTION

Explains the necessity of trapping the drain line and the required trap depth.

SUPPLY AIR BLOWER ADJUSTMENT

Guides on adjusting blower RPM based on CFM, accessories, and static resistance.

POWER AND CONTROL WIRING

WIRING INSTALLATION AND ROUTING

Install wiring per NEC/local codes, ground unit, and route wires through knockouts.

MOTOR ROTATION AND ELECTRIC HEAT WIRING

Check/reverse motor rotation; refer to electric heat accessory instructions.

Overview

This document describes the installation, operation, and maintenance of Split-System Heat Pumps Indoor Units, specifically models FCHP090 and FDHP120.

Function Description:

These units are completely assembled indoor units designed for use in split-system heat pump applications. They include a well-insulated cabinet, a copper tube/aluminum fin coil, throw-away filters, a centrifugal blower, a blower motor, an adjustable V-belt drive, a blower motor contactor, and a small holding charge of an inert gas. They also feature a filter-drier, an expansion valve, and a distributor for the cooling cycle, plus a check valve for proper refrigerant flow during both cooling and heating cycles. These units are designed to provide conditioned air for indoor spaces, working in conjunction with a matching outdoor unit.

Important Technical Specifications:

  • Models: FCHP090 (7-1/2 Ton Nominal Cooling Capacity @ 60 Hz) and FDHP120 (10 Ton Nominal Cooling Capacity @ 60 Hz).
  • Coil:
    • FCHP090: 3 rows deep x 24 rows high, 45.5 inches finned length, 7.6 sq ft face area.
    • FDHP120: 4 rows deep x 32 rows high, 45.5 inches finned length, 10.1 sq ft face area.
    • Common: 3/8 inch copper tube OD, 13 aluminum fins per inch.
  • Centrifugal Blower: Forward Curve type, 15 x 15 inches diameter x width.
  • Blower Motor:
    • FCHP090: 1-1/2 HP nominal rating.
    • FDHP120: 2 HP nominal rating.
    • Common: 1750 RPM, solid base, 56 frame, 1.15 service factor, inherent protection, permanently lubricated ball bearings.
  • Filters: Throwaway type, 16" x 25" x 1" (4 per unit), total face area 11.1 sq ft.
  • Refrigerant: R-22.
    • FCHP090: 12.0 lbs pumpdown capacity.
    • FDHP120: 22.0 lbs pumpdown capacity.
  • Unit Weight (Shipping/Operating):
    • FCHP090: 405 lbs (shipping), 365 lbs (operating).
    • FDHP120: 440 lbs (shipping), 400 lbs (operating).
  • Accessory Operating Weights (Lbs.):
    • Electric Heaters: 10 KW (63-66 lbs), 16 KW (66-71 lbs), 26 KW (71-74 lbs), 36 KW (74-74 lbs).
    • Supply Air Plenum: 102 lbs.
    • Base: 60 lbs.
    • Return Air Grille: 15 lbs.
  • Voltage Codes: -S = 208/230/460-3-60.
  • Application Data (Entering Air Temperatures):
    • Cooling (wb): 57-72°F.
    • Heating (db): 50-80°F (system may operate below 50°F for short periods during warm-up).
  • Supply Air CFM:
    • FCHP090: 2400-3600 CFM.
    • FDHP120: 3200-4800 CFM.
  • Electrical Data (FLA, Max Fuse Size, Max Wire Length):
    • FCHP090 (1-1/2 HP): 208V (5.3 FLA, 10A fuse, 207ft wire), 230V (5.8 FLA, 10A fuse, 209ft wire), 460V (2.7 FLA, 5A fuse, 897ft wire).
    • FDHP120 (2 HP): 208V (7.5 FLA, 10A fuse, 146ft wire), 230V (6.8 FLA, 10A fuse, 178ft wire), 460V (3.4 FLA, 5A fuse, 712ft wire).
  • Control Wire Sizing: Ranges from #19 Solid (130 ft) to #12 Stranded (730 ft) depending on total circuit length.

Usage Features:

  • Installation Flexibility: Units are shipped for vertical installation but can be converted for horizontal installation by reversing the solid bottom panel and the return air duct flange.
  • Mounting Options: Can be set directly on a floor or platform, or suspended from above using four 3/8"-16 weld nuts provided in the unit frame for horizontal installations.
  • Accessory Integration: Designed to accommodate field-installed accessories such as supplemental resistance heaters, a supply air plenum, a return air grille, and a base.
  • Duct Connections: Ductwork should be sized no smaller than the unit flanges or electric heater flanges. Flexible collars are recommended to minimize noise and vibration.
  • Refrigerant Piping: Uses hard drawn copper tubing, with long radius ells recommended. Brazing with Sil-Fos 5 or equivalent is required for copper-to-copper joints. The vapor line must be insulated.
  • Drain Connection: A 7/8" OD drain connection extends through the right-hand side of the cabinet. A trap at least 2-1/2" deep is required to prevent condensate overflow due to negative static pressure from the blower.
  • Blower Adjustment: Features an adjustable V-belt drive and motor pulley to fine-tune supply air CFM based on system requirements. Pulleys are factory-aligned and set to 3 "turns open" but can be adjusted in half-turn increments.
  • Clearances: Minimum clearances are specified for proper operation and service, including 24" for return air and supply air openings, 52" for piping connections, 12" for the side opposite piping, and sufficient clearance for power/control wiring and drain line trapping at the bottom.
  • Safety: Includes warnings about proper rigging, handling, and the importance of adhering to national and local safety codes, as well as precautions against improper installation leading to injury or property damage. Provisions for refrigerant recovery are emphasized.

Maintenance Features:

  • Indoor Coil Cleaning: Regular cleaning is necessary to ensure good system performance. Dirt accumulation can be removed with a brush, vacuum cleaner, or, if extremely dirty, an industrial-grade detergent and hose.
  • Drain Pan Inspection: The condensate drain pan should be inspected regularly to ensure proper drainage and prevent overflow.
  • Filter Replacement: Filters must be replaced as often as necessary to maintain good airflow and filtering action, preventing loss of capacity and efficiency. The filter access panel location is shown in the unit drawing.
  • Lubrication: Blower shaft and motor bearings are permanently lubricated and do not require additional lubricant.
  • Belt Maintenance: Belt tension should be maintained to extend belt life. Belts should be replaced when signs of failure appear.
  • Blower Motor Pulley Adjustment: After initial installation and balancing, the supply air motor pulley may need readjustment if the CFM is outside specified values. Regular checks for belt tightness and alignment are recommended.
  • Troubleshooting: Instructions are provided for checking supply air CFM using an inclined manometer and a pressure drop curve, as well as for correcting blower rotation direction by reversing motor leads.
  • Owner Education: Installers are instructed to secure owner's approval and teach them about disconnect switches, thermostat operation, temperature settings, defrost cycle control, and anti-cycle timer.

York FCHP090 Specifications

General IconGeneral
BrandYork
ModelFCHP090
CategoryHeat Pump
LanguageEnglish

Related product manuals