036-21121-002 Rev. B (0103)
Unitary Products Group 19
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA076S(25,46)
INDOOR COIL MODEL NO. K4EV090
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 2100 2600 3100
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
75
T.C. 79.1 76.3 73.9 82.0 79.2 76.9 84.9 82.0 79.9
S.C. 48.8 48.6 48.1 55.4 55.3 54.7 62.0 61.9 61.3
K.W 5.98 5.90 5.84 6.28 6.18 6.15 6.58 6.48 6.46
85
T.C. 76.4 73.7 70.6 79.1 76.3 73.4 81.7 79.0 76.2
S.C. 47.9 47.6 46.8 54.7 54.4 53.5 61.5 61.2 60.3
K.W 6.53 6.42 6.37 6.86 6.74 6.70 7.18 7.07 7.04
95
T.C. 73.8 71.1 67.2 76.1 73.5 69.9 78.4 75.9 72.6
S.C. 47.1 46.7 45.4 54.0 53.6 52.4 60.9 60.4 59.4
K.W 7.08 6.94 6.90 7.43 7.30 7.26 7.79 7.65 7.61
105
T.C. 71.1 67.4 62.6 73.1 69.7 65.2 75.1 72.0 67.7
S.C. 46.4 45.4 43.7 53.1 52.2 50.5 59.8 58.9 57.2
K.W 7.84 7.70 7.61 8.21 8.08 7.99 8.57 8.46 8.36
115
T.C. 68.4 63.7 58.0 70.0 67.0 60.4 71.7 68.2 62.9
S.C. 45.4 44.1 42.0 52.0 51.9 48.5 58.6 57.5 55.0
K.W 8.59 8.46 8.32 8.97 8.80 8.71 9.36 9.28 9.10
125
T.C. 65.6 60.1 53.4 67.0 64.3 55.7 68.4 64.3 58.1
S.C. 44.5 42.7 40.2 51.0 51.6 46.5 57.5 56.0 52.8
K.W 9.35 9.21 9.02 9.74 9.51 9.43 10.14 10.09 9.84
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Coil
T.C. S.C. KW
G2FD090(S,H)35 1.00 0.99 1.01