Table 16: Heating performance data - 5 ton - air temperature (°F) entering outdoor unit
Outdoor unit model: HMH72B601S
ID CFMAir temperature (°F)
1500 1750 2000
Entering
outdoor unit
Entering
indoor coil
MBH COP kW MBH COP kW MBH COP kW
60 37.6 2.65 4.16 39.0 2.73 4.18 40.4 2.82 4.20
70 34.9 2.34 4.38 35.7 2.37 4.41 38.7 2.56 4.43
17
80 31.5 2.00 4.62 34.3 2.14 4.69 37.0 2.28 4.76
60 33.6 2.44 4.04 35.1 2.52 4.07 36.6 2.61 4.11
70 30.9 2.14 4.23 31.6 2.17 4.27 34.6 2.35 4.31
10
80 27.1 1.79 4.45 29.9 1.93 4.53 32.6 2.07 4.62
60 27.8 2.12 3.85 29.5 2.21 3.91 31.1 2.30 3.97
70 25.2 1.84 4.02 25.7 1.85 4.08 28.7 2.03 4.14
0
80 20.8 1.45 4.20 23.6 1.60 4.31 26.3 1.75 4.42
Note:
All capacities include indoor fan heat. kW values are for the system (outdoor + indoor).
21YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump
Johnson Controls Ducted Systems

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York HMH7 Series and is the answer not in the manual?

York HMH7 Series Specifications

General IconGeneral
SEER RatingUp to 18
RefrigerantR-410A
Voltage208/230V
Capacity Range1.5 to 5 tons
Sound LevelsAs low as 72 dBA
StagesSingle-Stage