Table 16: Heating performance data - 5 ton - air temperature (°F) entering outdoor unit
Outdoor unit model: HMH72B601S
ID CFMAir temperature (°F)
1500 1750 2000
Entering
outdoor unit
Entering
indoor coil
MBH COP kW MBH COP kW MBH COP kW
60 37.6 2.65 4.16 39.0 2.73 4.18 40.4 2.82 4.20
70 34.9 2.34 4.38 35.7 2.37 4.41 38.7 2.56 4.43
17
80 31.5 2.00 4.62 34.3 2.14 4.69 37.0 2.28 4.76
60 33.6 2.44 4.04 35.1 2.52 4.07 36.6 2.61 4.11
70 30.9 2.14 4.23 31.6 2.17 4.27 34.6 2.35 4.31
10
80 27.1 1.79 4.45 29.9 1.93 4.53 32.6 2.07 4.62
60 27.8 2.12 3.85 29.5 2.21 3.91 31.1 2.30 3.97
70 25.2 1.84 4.02 25.7 1.85 4.08 28.7 2.03 4.14
0
80 20.8 1.45 4.20 23.6 1.60 4.31 26.3 1.75 4.42
Note:
• All capacities include indoor fan heat. kW values are for the system (outdoor + indoor).
21YORK Technical Guide: HMH7 Series - 17 SEER Horizontal Discharge Modulating Heat Pump
Johnson Controls Ducted Systems