AIRFLOW DATA - UPFLOW MODELS: P*UR/FG9-UP/G9T-UP
MODELS
Input/Output/Airflow/
cabinet
SPEED TAP
EXTERNAL STATIC PRESSURE, INCHES WC
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
40 / 37 / 800 / A
HI 1051 1005 977 985 835 757 665 450
MED 900 887 851 810 752 693 609 403
LOW 581 577 569 542 468
60 / 55 / 1000 / B
HI 1220 1200 1190 1152 1115 1065 1012 950 872 771
MED 920 915 900 880 842 803 740 650
LOW 725 729 715 700 681 653 600 525
80 / 75 / 1200 / B
HI 1431 1395 1355 1317 1263 1226 1165 1101 1029 937
MED 1188 1076 1065 1046 1023 994 955 906 842 752
LOW 832 823 811 805 794 766 742 672 624 561
100 / 75 / 1600 / C
HI 1879 1837 1794 1740 1688 1627 1559 1485 1406 1314
MED 1379 1374 1348 1340 1313 1271 1232 1158 1978
LOW 1196 1181 1141 1095 1053 1001 936
100 / 95 / 1400 / C
HI 1742 1672 1602 1519 1433 1348 1232 1098 934 766
MED 1390 1360 1320 1265 1176 1082 965 810 656
LOW 1097 1061 1035 1000 927 830 708 574
100 / 95 / 2000 / C
HI 2300 2229 2168 2100 2026 1939 1855 1758 1661 1546
MED 1937 1897 1855 1808 1737 1673 1597 1511 1425 1305
LOW 1579 1564 1533 1481 1461 1415 1350 1291 1205 1093
120 / 112 / 2000 / D
HI 2366 2298 2226 2153 2065 1988 1890 1808 1712 1600
MED 2000 1961 1920 1874 1821 1757 1685 1606 1510 1430
LOW 1588 1578 1545 1525 1492 1455 1399 1340 1260 1163
140 / 130 / 2000 / D
HI 2343 2275 2204 2132 2047 1968 1871 1791 1695 1585
MED 1981 1942 1901 1856 1803 1740 1669 1591 1490 1416
LOW 1575 1562 1530 1510 1477 1440 1386 1327 1248 1152
Airflow expressed in standard cubic feet per minute.
Notes: 1. Return air is through side opposite motor (left side).
2. Air flows above 1800 CFM require either return from two sides or one side plus bottom.
3. Air filter installed. All filters must be high velocity, cleanable type.
4. Motor voltage at 115 V.
AIRFLOW DATA - DOWNFLOW/HORIZONTAL MODELS: P*DH/FG9-DH/G9T-DH
MODELS
Input/Output/Airflow/
cabinet
SPEED TAP
EXTERNAL STATIC PRESSURE, INCHES WC
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
40 / 37 / 800 / A
HI 1182 1164 1136 1101 1063 1018 967 904 824 724
MED 954 938 919 899 876 838 798 744 686 588
LOW 650 643 634 620 602 577 542 494 440 335
60 / 55 / 1200 / B
HI 1567 1552 1532 1517 1484 1441 1384 1315 1243 1166
MED 1175 1173 1169 1159 1144 1126 1089 1039 985 910
LOW 881 879 871 861 842 826 795 756 724 664
80 / 75 / 1200 / B
HI 1603 1579 1558 1522 1485 1433 1380 1311 1233 1139
MED 1250 1230 1210 1190 1160 1125 1083 1029 955 889
LOW 925 904 891 873 845 829 793 761 685 618
80 / 75 / 1600 / C
HI 2024 1960 1911 1855 1780 1698 1627 1540 1458 1387
MED 1479 1471 1465 1452 1429 1393 1359 1300 1238 1163
LOW 1210 1208 1198 1175 1149 1110 1052 982
100 / 95 / 2000 / C
HI 2272 2200 2128 2061 1984 1890 1810 1710 1627 1519
MED 1980 1933 1887 1838 1769 1701 1626 1535 1426 1328
LOW 1573 1546 1526 1498 1464 1417 1359 1290 1222 1132
120 / 112 / 2000 / D
HI 2281 2215 2144 2065 2002 1903 1820 1720 1618 1505
MED 1945 1902 1849 1794 1738 1675 1604 1535 1426 1343
LOW 1507 1485 1463 1433 1398 1358 1305 1249 1172 1095
Airflow expressed in standard cubic feet per minute.
Notes: 1. Air filter installed. All filters must be high velocity, cleanable type.
2. Motor voltage at 115 V.