650.75-N4U 035-14370-000
6 Unitary Products Group
TABLE 1: RATINGS & PHYSICAL / ELECTRICAL DATA - UPFLOW MODELS (P*UR/FG9-UP/G9T-UP)
MODELS P*UR/FG9-UP/
G9T—UP
CABINET
WIDTH
AFUE
1
A
IR
TEMP
RISE
°
F
CFM
@
MEAN
AIR
TEMP
RISE
MAX
.
OUTLET
AIR
TEMP
. °
F
BLOWER
TOTAL
UNIT
AMPS
MAX
OVER
-
CURRENT
PROTECT
2
MIN
WIRE
SIZE
(
AWG
)
@ 75
FT
.
ONE
WAY
2
INPUT
MBH
OUTPUT
MBH
NOM
.
CFM
DIA
(
IN
)
WIDTH
(
IN
.)
HP
40 37 800 14-1/2 92.4 35 - 65 685 165 9 6 1/4 9.0 20 14
60 55 1000 17-1/2 92.2 45 - 75 850 175 10 6 1/3 9.0 20 14
80 74 1200 17-1/2 92.0 35 - 65 1160 165 11 8 1/2 9.0 20 14
80 76 1600 21 94.3 30 - 60 1540 160 11 8 3/4 12.0 20 14
100 93 1400 21 92.2 45 - 75 1465 175 10 10 1/2 9.0 20 14
100 94 2000 21 93.0 30 - 60 1955 160 11 10 1 12.0 20 14
120 112 2000 24-1/2 92.0 45 - 75 1730 175 11 10 1 12.0 20 14
140 130 2000 24-1/2 92.0 45 - 75 2005 175 11 10 1 12.0 20 14
1.
AFUE numbers are determined in accordance with DOE test procedures
2.
Wire size and overcurrent protection must comply with the National Electrical Code (NFPA-70-latest edition).
For altitudes above 2,000 ft., reduce capacity 4% for each 1,000 ft. above sea level. Refer to Form 650.74-N1.1V.
Wire size based on copper conductors, 60°C, 3% voltage drop.
Continuous return air temperature must not be below 55°F.
B
3/4
28-1/2
A
20
45
FRO N T LEFT SIDE
RIGHT SIDE
OPTIONAL SIDE
RETURN CUT-OUT
(EITHER SIDE)
14-1/2
1-3/4
1
3/
4
1-1/4
22-3/4
6-7/8
3-1/4
7-5/8
POW ER W IRING
T'STAT W IRING
7/8" K.O .
CONDENSATE
DRAIN
7/8" H O LE
4-1/8
G A S O U T L E T
1-1/4" X 2-1/2"
(A ll gas pipe
connections 1/2" N P T)
1-3/4
9-7/8
7-5/8
Models P*XU &
G9D—UH
A
60 / 55 / 1200 / “B”
17-1/2 16
80 / 75 / 1200 / “B”
17-1/2 16
80 / 75 / 1600 / “C” 21 19
100 / 95 / 1400 / “C” 21 19
100 / 95 /2000 / “C 21 19
120 / 112 / 2000 / “D” 24-1/2 23
1.
Vent pipe must be increased
TO P IM AG E
Vent C onnection
E
(v e n t s iz e )
B
FRO N T
In ta k e
C
onnection
D
20
BO TTO M IM AG E
(F R O N T )
23
C
3/4"
FLANG E
A
28-1/2
(W IT H K .O .
REM OVED)
B
3/4
28-1/2
A
20
45
FRO N T LEFT SIDE
RIGHT SIDE
OPTIONAL SIDE
RETURN CUT-OUT
(EITHER SIDE)
14-1/2
1-3/4
1
3/
4
1-1/4
22-3/4
6-7/8
3-1/4
7-5/8
POW ER W IRING
T'STAT W IRING
7/8" K.O .
CONDENSATE
DRAIN
7/8" H O LE
4-1/8
G A S O U T L E T
1-1/4" X 2-1/2"
(A ll gas pipe
connections 1/2" N P T)
1-3/4
9-7/8
7-5/8
TO P IM AG E
Vent C onnection
E
(v e n t s iz e )
B
FRO NT
In ta k e
C
onnection
D
20
BO TTO M IM AG E
(F R O N T )
23
C
3/4"
FLAN G E
A
28-1/2
(W IT H K .O .
REM O VED)
Models P*UR/
FG9-UP/G9T—UP
ABCDE
40 / 37 / 800 / A 14-1/2
12-3/4
10-1/8 2 2
60 / 55 / 1000 / B 17-1/2
16-1/4
13-1/8 2 2
80 / 75 / 1200 / B 17-1/2
16-1/4
13-1/8 2 2
80 / 75 / 1600 / C 21
19-3/4
16-5/8 2 2
100 / 95 / 1400 / C 21
19-3/4
16-5/8 2 2
100 / 95 / 2000 / C 21
19-3/4
16-5/8 2 2
120 / 112 / 2000 / D 24-1/2
23-1/4
20-1/8 3
2 (3)
1
1.
Vent pipe must be increased to 3” on this model.
140 / 130 / 2000 / D 24-1/2
23-1/4
20-1/8 3
2 (3)
ALL DIMENSIONS ARE IN INCHES, AND ARE
APPROXIMATE.
FIGURE 1 :
DIMENSIONS - UPFLOW MODELS: P*UR/FG9-UP/G9T-UP