5005562-YTG-A-0215
14 Johnson Controls Unitary Products
1. Airflow tested with dry coil conditions, without air flitters, at 230 volts
2. Applications above 0.8" w.c. external static pressure are not recommended.
3. Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
4. Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
48100
Low (1) 1620 1564 1517 1466 1418 1360 1308 1206
Low/Medium (2) 1694 1630 1580 1530 1482 1430 1380 1292
Medium (3) 1798 1722 1669 1620 1572 1527 1480 1413
Medium/High (4) 1835 1758 1703 1653 1604 1558 1511 1442
High (5) 2146 2085 2025 1960 1872 1862 1798 1735
48125
Low (1) 1620 1564 1517 1466 1418 1360 1308 1206
Low/Medium (2) 1798 1722 1669 1620 1572 1527 1480 1413
Medium (3) 1922 1863 1804 1754 1724 1658 1612 1559
Medium/High (4) 2001 1952 1890 1839 1820 1742 1696 1651
High (5) 2146 2085 2025 1960 1872 1862 1798 1735
60065
Low (1) 1073 1043 1009 988 963 941 917 892
Low/Medium (2) 1329 1292 1250 1223 1192 1165 1136 1105
Medium (3) 2054 1998 1934 1890 1843 1801 1757 1710
Medium/High (4) 2195 2144 2098 2049 2003 1955 1883 1868
High (5) 2445 2388 2306 2293 2235 2178 2129 2077
60100
Low (1) 1730 1682 1628 1592 1552 1517 1479 1439
Low/Medium (2) 1858 1807 1749 1710 1667 1629 1589 1546
Medium (3) 2054 1998 1934 1890 1843 1801 1757 1710
Medium/High (4) 2195 2144 2098 2049 2003 1955 1883 1868
High (5) 2445 2388 2306 2293 2235 2178 2129 2077
60125
Low (1) 2063 2008 1943 1899 1851 1809 1763 1717
Low/Medium (2) 2130 2084 2032 1983 1927 1951 1860 1815
Medium (3) 2195 2144 2098 2049 2003 1955 1883 1868
Medium/High (4) 2275 2252 2169 2154 2112 2065 1989 1976
High (5) 2445 2388 2306 2293 2235 2178 2129 2077
Airflow - Side Duct Application (Continued)
Model Motor Speed
External Static Pressure (Inches WC)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM