EXTERNAL STATIC PRESSURE SETUP
To measure external static pressure:
Measure the supply air static pressure
Record this positive number
Measure the return air static pressure
Record this negative number
Treat the negative number as a positive and add the two numbers together
This is total system static
UNIT TYPICAL ROOF CURB INSTALLATION
SUPPLY
AIR DUCT
TO POWER SUPPLY
RETURN
AIR DUCT
FIELD-SUPPLIED
DISCONNECT
SWITCH
CONTROL WIRING TO
INDOOR THERMOSTAT
TO GAS
SUPPLY LINE
MANUAL GAS
SHUTOFF VAVLE
ROOF CURB
ROOF
CONDENSATE
DRAIN
A0326-001