Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive Standard 2 HP & Drive Hi Static 3 HP & Drive
2600 722 0.83 776 0.97 828 1.11 878 1.25 926 1.37 973 1.50 1018 1.62 1063 1.74 1106 1.86 1149 1.99
2800 744 0.97 798 1.12 850 1.26 900 1.39 949 1.52 995 1.64 1041 1.76 1085 1.88 1128 2.00 1171 2.13
3000 769 1.13 823 1.28 875 1.42 925 1.55 974 1.68 1020 1.80 1066 1.92 1110 2.05 1153 2.17 1196 2.29
3200 797 1.32 851 1.46 903 1.60 953 1.74 1001 1.86 1048 1.99 1093 2.11 1138 2.23 1181 2.35 1224 2.48
3400 828 1.52 882 1.67 934 1.81 983 1.94 1032 2.07 1078 2.19 1124 2.32 1168 2.44 1212 2.56 1254 2.68
3600 861 1.75 915 1.90 967 2.04 1017 2.17 1065 2.30 1112 2.42 1157 2.54 1201 2.67 1245 2.79 1287 2.91
3800 897 2.00 951 2.15 1002 2.29 1052 2.42 1101 2.55 1147 2.67 1193 2.80 1237 2.92 1280 3.04 1323 3.16
4000 935 2.27 989 2.42 1041 2.56 1091 2.69 1139 2.82 1186 2.95 1231 3.07 1275 3.19 1319 3.31 1362 3.43
4200 976 2.57 1030 2.72 1082 2.86 1132 2.99 1180 3.12 1227 3.24 1272 3.36 - -----
4400 1019 2.88 1073 3.03 1125 3.17 1175 3.30 1223 3.43 - - - - - -----
460010653.2211193.36----------------
3 HP & Field Supplied Drive
ZH150 (12.5 Ton) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP & Field Supplied Drive Standard 3 HP & Drive Hi Static 5 HP & Drive
3200 797 1.32 851 1.46 903 1.60 953 1.74 1001 1.86 1048 1.99 1093 2.11 1138 2.23 1181 2.35 1224 2.48
3400 828 1.52 882 1.67 934 1.81 983 1.94 1032 2.07 1078 2.19 1124 2.32 1168 2.44 1212 2.56 1254 2.68
3600 861 1.75 915 1.90 967 2.04 1017 2.17 1065 2.30 1112 2.42 1157 2.54 1201 2.67 1245 2.79 1287 2.91
3800 897 2.00 951 2.15 1002 2.29 1052 2.42 1101 2.55 1147 2.67 1193 2.80 1237 2.92 1280 3.04 1323 3.16
4000 935 2.27 989 2.42 1041 2.56 1091 2.69 1139 2.82 1186 2.95 1231 3.07 1275 3.19 1319 3.31 1362 3.43
4200 976 2.57 1030 2.72 1082 2.86 1132 2.99 1180 3.12 1227 3.24 1272 3.36 1316 3.48 1360 3.60 1402 3.73
4400 1019 2.88 1073 3.03 1125 3.17 1175 3.30 1223 3.43 1270 3.55 1315 3.67 1360 3.80 1403 3.92 1446 4.04
4600 1065 3.22 1119 3.36 1171 3.50 1221 3.64 1269 3.76 1316 3.89 1361 4.01 1405 4.13 1449 4.25 1491 4.38
4800 1113 3.57 1167 3.72 1219 3.86 1269 3.99 1317 4.12 1364 4.24 1409 4.36 1453 4.48 1497 4.61 1540 4.73
5000 1163 3.94 1217 4.09 1269 4.23 1319 4.36 1367 4.49 1414 4.62 1459 4.74 1504 4.86 1547 4.98 1590 5.10
5200 1216 4.34 1270 4.48 1321 4.62 1371 4.76 1420 4.88 1466 5.01 1512 5.13 1556 5.25 1600 5.37 1642 5.50
5400 1270 4.75 1324 4.89 1376 5.03 1426 5.17 1474 5.29 1521 5.42 1566 5.54 1611 5.66 ----
5600 1327 5.17 1381 5.32 1433 5.46 1483 5.59 1531 5.72 - - - - - -----
580013855.62------------------