TECHNICAL GUIDE
AFFINITY
MODELS: PT8-UH
GAS-FIRED
HIGH EFFICIENCY TWO STAGE
UPFLOW/HORIZONTAL FURNACES
STANDARD & Low NOx
80% AFUE
NATURAL GAS
40 - 120 MBH INPUT
Due to continuous product improvement,
specifications are subject to change without notice.
Visit us on the web at www.york.com for the most
up-to-date technical information.
Additional rating information can be found at
www.gamanet.org.
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
246755-YTG-D-0407
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION
These high efficiency, compact units employ induced com-
bustion, reliable hot surface ignition and high heat transfer
aluminized tubular heat exchangers. The units are factory
shipped for installation in upflow or horizontal applications.
These furnaces are designed for residential installation in a
basement, closet, alcove, attic, recreation room or garage
and are also ideal for commercial applications. All units are
factory assembled, wired and tested to assure safe depend-
able and economical installation and operation.
These units are Category I listed and may be common
vented with another gas appliance as allowed by the
National Fuel Gas Code.
WARRANTY
20-year limited warranty on the heat exchanger.
10-year heat exchanger warranty on commercial applica-
tions.
5-year limited parts warranty.
FEATURES
Two stage heating operation includes:
- Two stage gas valve
- Two stage inducer operation
- Two speed blower operation
Provides increased comfort level & very quiet unit oper-
ation
Adjustable delay timer allows two stage operation with
single stage thermostat
Compact, easy to install, ideal height 40" cabinet
Blower-off delay for cooling SEER improvement.
Easy to connect power/control wiring.
Built-in, high level self diagnostics with fault code display.
Low unit amp requirement for easy replacement applica-
tion.
Integrated control module for reliable, economical opera-
tion.
Electronic Hot Surface Ignition saves fuel cost with
increased dependability and reliability.
Induced combustion system with inshot main burners for
quiet, efficient operation.
100% shut off main gas valve for extra safety.
PSC -four speed, direct drive motor with large, quiet
blower.
24V, 40 VA control transformer and blower relay supplied
for add-on cooling.
Hi-tech tubular aluminized steel primary heat exchanger.
Timed on, adjustable off blower capability for maximum
comfort.
Solid removable bottom panel allows easy application.
Easy access from front of unit for cleaning, maintenance
or service.
Insulated blower compartment for quiet operation.
Independent door removal for greater durability and ease
of access.
Low NOx models have been designed to meet specific
code requirements.
Low NOx models may not be converted to propane unless
screens are removed.
Question and Answer IconNeed help?

Do you have a question about the York PT8-UH and is the answer not in the manual?

Summary

Key Features and Benefits

Ratings and Electrical Data

Blower Performance Data

Upflow Bottom Return Airflow

Table showing CFM output for various models at different static pressures and speed settings.

Blower Performance - Left Side Return

Upflow Left Side Return Airflow

Table detailing CFM output for different models with left side return, across static pressures and speeds.

Applying Filter Pressure Drop

System Airflow Calculation

Step-by-step guide on how to determine system airflow with filters, including an example calculation.

Thermostat Wiring Diagrams

AC System Connections

Illustrates thermostat wiring for 2-stage cooling ready furnaces with various thermostat models.

Heat Pump Thermostat Wiring

Overview

This document describes the YORK Affinity Series PT8-UH gas-fired, high-efficiency two-stage upflow/horizontal furnaces, designed for both standard and Low NOx applications. These furnaces operate at 80% AFUE (Annual Fuel Utilization Efficiency) and are available for natural gas with inputs ranging from 40 to 120 MBH.

Function Description:

These furnaces are designed for residential and commercial heating applications, providing efficient and reliable warmth. They utilize induced combustion, hot surface ignition, and high heat transfer aluminized tubular heat exchangers. The two-stage operation, including a two-stage gas valve, two-stage inducer, and two-speed blower, ensures enhanced comfort and quiet operation. The units are factory-assembled, wired, and tested for safe, dependable, and economical installation. They are Category I listed, allowing for common venting with other gas appliances as per the National Fuel Gas Code.

Important Technical Specifications:

  • AFUE: 80%
  • Fuel Type: Natural Gas (convertible to Propane (LP) with accessory kit 1NP0347, but Low NOx models cannot be converted to propane unless screens are removed).
  • Input Range: 40-120 MBH
  • Cabinet Height: 40 inches
  • Cabinet Widths: 14.5, 17.5, 21 inches
  • Blower Motor: PSC, four-speed, direct drive (1/2 HP, 3/4 HP, 1 HP options)
  • Control Transformer: 24V, 40 VA
  • Heat Exchanger: Hi-tech tubular aluminized steel primary heat exchanger.
  • Electrical: 115V motor voltage. Max over-current protection ranges from 20A. Min. wire size (AWG) @ 75 ft ranges from 12 to 14.
  • Airflow: Ranges from 710 to 2770 SCFM depending on model, speed, and external static pressure.
  • Temperature Rise: Low fire air temperature rise ranges from 15-55°F, high fire air temperature rise ranges from 20-75°F.
  • Max Outlet Air Temperature: Ranges from 150-180°F.
  • Clearances to Combustibles (Upflow/Horizontal):
    • Top: 1 inch
    • Front: 6 inches
    • Rear: 0 inches
    • Left Side: 0 inches (Upflow B-Vent), 3 inches (Upflow/Horizontal)
    • Right Side: 3 inches (Upflow/Horizontal), 0 inches (Upflow B-Vent)
    • Flue: 6 inches (Upflow/Horizontal), 1 inch (Upflow B-Vent)
    • Floor/Bottom: Combustible (Upflow), Combustible (Upflow B-Vent), Combustible (Horizontal), Combustible (Horizontal B-Vent)
    • Line Contact: No (Upflow/Upflow B-Vent), Yes (Horizontal/Horizontal B-Vent) - Line contact permitted between rear panel/side panel intersection and building joists/studs/framing.
  • Horizontal Venting: Approved with auxiliary power vents (Fields Controls Model SWG-4Y or Tjernlund GPAK model). Uses 4" (10.2 cm) diameter pipe with a minimum length of 4.5 feet (1.37 m) and a maximum length of 34.5 feet (10.82 m) with up to 4 elbows.

Usage Features:

  • Compact Design: Ideal 40" cabinet height for easy installation in various residential and commercial settings (basement, closet, alcove, attic, recreation room, garage).
  • Two-Stage Heating: Provides consistent comfort and quiet operation by adjusting heating output based on demand.
  • Adjustable Delay Timer: Allows two-stage operation even with a single-stage thermostat.
  • Blower-Off Delay: Improves cooling SEER (Seasonal Energy Efficiency Ratio).
  • Easy Wiring: Simple connection for power and control wiring.
  • Self-Diagnostics: Built-in high-level diagnostics with fault code display for quick troubleshooting.
  • Low Unit Amp Requirement: Facilitates easy replacement applications.
  • Integrated Control Module: Ensures reliable and economical operation.
  • Electronic Hot Surface Ignition: Enhances dependability and fuel efficiency.
  • Induced Combustion System: Features inshot main burners for quiet, efficient operation.
  • 100% Shut-Off Main Gas Valve: Provides extra safety.
  • PSC Blower Motor: Large, quiet blower with four speeds.
  • Add-on Cooling Support: Supplied with 24V, 40 VA control transformer and blower relay.
  • Timed On/Adjustable Off Blower: Maximizes comfort.
  • Solid Removable Bottom Panel: Allows for flexible application.
  • Insulated Blower Compartment: Contributes to quiet operation.
  • Independent Door Removal: Enhances durability and ease of access.
  • Thermostat Compatibility: Wide selection of compatible thermostats available, including manual, non-programmable electronic, and programmable deluxe 7-day options for 1 heat stage, 1 heat/1 cool, and multi-stage systems.
  • High Altitude Pressure Switches: Available for altitudes above 8,000 feet (1PS0313 for 40-100 MBH, 1PS0314 for 120 MBH).

Maintenance Features:

  • Easy Front Access: Convenient access from the front of the unit for cleaning, maintenance, or service.
  • Filter Options: Supports disposable, washable fiber, and pleated filters. Recommended filter sizes vary by cabinet size and return configuration (side or bottom). Airflow data is provided for systems without filters, and a method for calculating airflow with filters is included, considering pressure drop values.
  • Accessory Filters: Side return filters (1SR0302, 1SR0200), bottom return filters (1BR0114/0214, 1BR0117/0217, 1BR0121/0221, 1BR0124/0224), and internal fiber filters (1HF0801) are available.