EasyManua.ls Logo

York R-410A - Technical Specification: High ESP Duct YDS-200-250 TC15 IA R-410 A 50 Hz

York R-410A
385 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
High ESP duct
___________________________________________________________________________________
___________________________________________________________________________________
- 223 -
2. Specification
Technical specification: High ESP duct YDS-200-250TC15IA R-410A 50Hz
Model
YDS-200TC15IA YDS-250TC15IA YDS-280TC15IA
Power supply Ph-V-Hz 1 Ph-220-240V-50Hz
Nominal capacity
Capacity kW
22.0 25.0 28.0
Cooling
Input kW
9.4 9.6 10
Capacity kW
22.6 27.5 31.1
Heating
Input kW
9.4 9.6 10
Motor
Input W
900/820/630(×2)
Capacitor uF
12(×2) 15(×2)
Speed (Hi/Me/Lo) r/min
1300/1100/900(×2)
Coil
a. Number of rows
4
b. Tube pitch(a)x row pitch(b) mm
25.4×22
c. Fin spacing mm
1.8
Hydrophilic aluminum
d. Fin type (code)
9.52
e. Tube outside dia. and type mm
Inner groove tube
f. Coil length x height x width mm
1125×512×88
g. Number of circuits
20
Performance
Noise level (Hi/Me/Lo) dB(A)
61/58/55
External static pressure Pa
196
Air flow (Hi/Me/Lo) m3/h
4180/3820/3200 4400/3940/3300
Piping size Liquid/ Gas side mm
Ф9.5/Ф15.9
Containerization
Unit (WxHxD) mm
1425×928×500
Packing(WxHxD) mm
1509×964×570
Dimensions
Net/Gross weight Kg
122/128
Qty per 20’/40’/40’HQ Pieces 24/48/48
Notes:
1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB, 19°CWB, and outdoor temperature: 35°CDB,
equivalent ref. piping: 8m (horizontal)
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, and
equivalent ref. Piping: 8m (horizontal)
3. Capacities are net, not including a deduction for cooling (an addition for heating) for indoor fan motor heat

Table of Contents