FORM 150.60-NM4
YORK INTERNATIONAL 57
FIG. 21 HISTORY PRINTOUT
NOTE: In actual print-outs, this would be one continuous print-out.
Shutdowns which occurred. The information is stored at
the instant of the fault regardless of whether the fault
caused a lockout to occur. The information is also not
affected by power failures (long term internal memory
battery back-up is built into the circuit board) or manual
resetting of a fault lock-out.
When the HISTORY key is pressed, a Printout is trans-
mitted of all system Operating conditions which were
stored at the instant the fault occurred for each of the 3
SAFETY SHUTDOWN BUFFERS. There is one buffer
(storage area) for data related to each of the last 3 safety
shutdowns.
The printout will begin with the most recent fault which
occurred. The most recent fault will always be stored as
SAFETY SHUTDOWN NO. 1 (See printout Fig. 21). Iden-
tically formatted fault information will then be printed for
SAFETY SHUTDOWN NO. 2 and SAFETY SHUTDOWN
NO. 3.
Information contained in the SAFETY SHUTDOWN Buff-
ers is very important when attempting to troubleshoot a
system problem. This data reflects the system condi-
tions at the instant the fault occurred and often reveals
other system conditions which actually caused the safety
threshold to be exceeded. (See Fig. 21)
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SAFETY SHUTDOWN NUMBER 1
SHUTDOWN @ 8:48AM 4/17/95
SYS 1 STATUS: NO FAULTS
SYS 2 MOTOR CURRENT SHUTDOWN
RETURN WATER TEMP 65.0 DEGF
LEAVING WATER TEMP 54.0 DEGF
LOW WATER CUTOUT 36.0 DEGF
SETPOINT TEMP 45.0 DEGF
OUTSIDE AIR TEMP 75.0 DEGF
LOW AMBIENT CUTOUT 10.0 DEGF
LOW PRESSURE CUTOUT 44 PSIG
LEAD SYSTEM SYS 1
CONTROL TYPE LCHWT
COOLING RANGE 45.0 TO 47.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS ON
MOTOR AMPS 5 0 %FLA
SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 14 3 PSIG
OIL PRESSURE 75 PSID
LIQUID LINE SOLENOID OFF
RUN PERMISSIVE ON
STAGES OF LOADING 1
FORWARD FANS 2
REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF
SYSTEM 2 DATA
COMPRESSOR STATUS ON
MOTOR AMPS 0 %FLA
SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 80 PSIG
OIL PRESSURE 1 PSID
LIQUID LINE SOLENOID OFF
RUN PERMISSIVE ON
STAGES OF LOADING 1
FORWARD FANS 1
REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SAFETY SHUTDOWN NUMBER 2
SHUTDOWN @ 8:47AM 4/17/95
SYS 1 STATUS: NO FAULTS
SYS 2 MOTOR CURRENT SHUTDOWN
RETURN WATER TEMP 65.0 DEGF
LEAVING WATER TEMP 54.0 DEGF
LOW WATER CUTOUT 36.0 DEGF
SETPOINT TEMP 45.0 DEGF
OUTSIDE AIR TEMP 75.0 DEGF
LOW AMBIENT CUTOUT 10.0 DEGF
LOW PRESSURE CUTOUT 44 PSIG
LEAD SYSTEM SYS 1
CONTROL TYPE LCHWT
COOLING RANGE 45.0 TO 47.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS ON
MOTOR AMPS 5 0 %FLA
SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 14 3 PSIG
OIL PRESSURE 75 PSID
LIQUID LINE SOLENOID ON
RUN PERMISSIVE ON
STAGES OF LOADING 1
FORWARD FANS 2
REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF
SYSTEM 2 DATA
COMPRESSOR STATUS ON
MOTOR AMPS 0 %FLA
SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 80 PSIG
OIL PRESSURE 1 PSID
LIQUID LINE SOLENOID OFF
RUN PERMISSIVE ON
STAGES OF LOADING 1
FORWARD FANS 1
REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SAFETY SHUTDOWN NUMBER 3
SHUTDOWN @ 8:47AM 4/17/95
SYS 1 STATUS: NO FAULTS
SYS 2 MOTOR CURRENT SHUTDOWN
RETURN WATER TEMP 65.0 DEGF
LEAVING WATER TEMP 54.0 DEGF
LOW WATER CUTOUT 36.0 DEGF
SETPOINT TEMP 45.0 DEGF
OUTSIDE AIR TEMP 75.0 DEGF
LOW AMBIENT CUTOUT 10.0 DEGF
LOW PRESSURE CUTOUT 44 PSIG
LEAD SYSTEM SYS 1
CONTROL TYPE LCHWT
COOLING RANGE 45.0 TO 47.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS ON
MOTOR AMPS 5 0 %FLA
SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 14 3 PSIG
OIL PRESSURE 75 PSID
LIQUID LINE SOLENOID ON
RUN PERMISSIVE ON
STAGES OF LOADING 1
FORWARD FANS 2
REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF
SYSTEM 2 DATA
COMPRESSOR STATUS ON
MOTOR AMPS 0 %FLA
SUCTION PRESSURE 61 PSIG
DISCHARGE PRESSURE 80 PSIG
OIL PRESSURE 1 PSID
LIQUID LINE SOLENOID OFF
RUN PERMISSIVE ON
STAGES OF LOADING 1
FORWARD FANS 1
REVERSE FANS OFF
HOT GAS BYPASS VALVE OFF