York SAC - Indoor units; Limits of use; Before final approval of the installation

York SAC
17 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
Minimum
14
220/240.3.50 14 5,2 4 x 2.5 -
380/415.3.50 7 2 4 x 2.5 -
220/240.3.50 23 5.5 4 x 2.5 -
380/415.3.50 10 3.2 4 x 2.5 -
220/240.3.50 23 5.7 4 x 2.5 -
380/415.3.50 10 3.3 4 x 2.5 -
380/415.3.50 10 3.5 4 x 2.5 -
380/415.3.50 27 7.1 4 x 2.5 15
380/415.3.50 30 6.4 4 x 2.5 15
Power supply V.ph.Hz. Consumption A
Fan
Model
Fan
Start Nominal
Power
supply cable
section
SOC-120/SOC-090/120
SOC-090/SIC-090/120
SIC-076
SIC-180
SIC-240
SIC-150
mm
2
A
Automatic
switch
Air intake temperature to
evaporating unit °C
Voltage limits
Nom. 220/240 V Nom. 380/415 V
Temperature WB Temperature DB
Temperature DB
Minimum
19
Minimum
198
Maximum
46
Maximum
32
Minimum
342
Maximum
436
Maximum
254
Maximum
23
Minimum
19
Air intake temperature to
condensing unit °C
Notes: WB -Wet Bulb, DB -Dry Bulb.
Indoor units
Limits of use
Before final approval of the installation
Verify:
-Voltage is always between 198-
254 V., or 342-436 V.
-The section of the power supply ca-
ble is, at least, that recommended in
the corresponding wiring diagrams.
-Condensation drainage is carried out
perfectly and there are no leaks in
the water circuit.
-Operating instructions have been
given to the user.
-The need to clean the air filter peri-
odically has been notified.
-The guarantee card has been filled
out.
-Maintenance instructions have
been given, or a regular servicing
contract has been signed.