251933-YTG-J-1009
Johnson Controls Unitary Products 91
060
(5.0)
208-3-60 15.6 110.0 24.4 2.3 8.2 10.0
None - - - 40.0 50
E05 4.0 1 11.1 53.9 60
E07 5.6 1 15.5 59.4 70
E10 8.0 1 22.2 67.8 70
E15 11.9 2 33.0 81.3 90
E20 15.9 2 44.1 95.2 100
E30 22.2 2 61.6 117.0 125
230-3-60 15.6 110.0 24.4 2.3 8.2 10.0
None - - - 40.0 50
E05 5.3 1 13.3 55.9 60
E07 7.5 1 18.8 62.6 70
E10 10.6 1 26.6 71.9 80
E15 15.9 2 39.9 87.8 90
E20 21.2 2 53.2 103.7 110
E30 29.6 2 74.3 129.0 150
460-3-60 7.7 52.0 12.1 1.3 4.1 5.0
None - - - 20.0 25
E07 6.8 1 8.5 30.2 35
E10 10.1 1 12.7 35.2 40
E15 13.6 2 17.1 40.5 45
E20 19.5 2 24.5 49.3 50
E30 28.8 2 36.1 63.3 70
575-3-60 5.8 38.9 9.1 1.3 3.6 4.0
None - - - 15.9 20
E10 10.6 1 10.6 28.6 30
E15 15.9 1 16.0 35.0 40
E20 21.2 2 21.3 41.4 45
E30 30.4 2 30.5 52.5 60
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
XP036-060 (Belt Drive High Static) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps