FORM 150.67-EG1 (219)
JOHNSON CONTROLS
7
All controls are contained in a NEMA 3R powder painted steel cabinet with a gasketed
door and include the following features:
Liquid Crystal Display (LCD) with Light Emitting Diode (LED) backlighting for outdoor
viewing:
Two display lines
Twenty characters per line
Color-coded 12-button non-tactile keypad with two sections:
DISPLAY/PRINT the following typical information:
Chilled liquid temperatures
Ambient temperature
System pressures (each circuit)
Operating hours and starts (each compressor)
PRINT displays the following information on the liquid crystal display:
Operating data for the systems
History of fault shutdown data for up to the last six fault shutdown condi-
tions
An RS-232 port, in conjunction with this press-to-print button, enables
hard copies to be printed via a seperate printer
ENTRY section to:
Enter setpoints or modify system values
SETPOINTS updating can be performed to:
Chill liquid temperature setpoint and range
Remotely reset temperature range
Set daily schedule/holiday for start/stop
Manually override for servicing
Low and high ambient cutouts
Number of compressors
Low liquid temperature cutout