EasyManua.ls Logo

York YCAL0028EE - Design Parameters

York YCAL0028EE
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FORM 150.67-EG1 (219)
JOHNSON CONTROLS
17
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls Ofce for ap-
plication requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest Johnson Controls Ofce for
application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
4. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed
on the system (for YCAL0043-0065 models only).
5. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be in-
stalled on the system.
Design Parameters
ENGLISH
YCAL
LEAVING WATER
TEMPERATURE (°F)
COOLER
FLOW (GPM)
AIR ON
CONDENSER (°F)
MIN MAX MIN MAX MIN MAX
0019EE 40 55 10 150 0 125
0022EE 40 55 10 150 0 125
0028EE 40 55 10 150 0 125
0033EE 40 55 10 150 0 125
0043EE 40 55 40 200 0 125
0046EE 40 55 40 200 0 125
0052EE 40 55 60 300 0 125
0056EE 40 55 60 300 0 125
0066EE 40 55 60 300 0 125
SI UNITS
YCAL
LEAVING WATER
TEMPERATURE (°C)
COOLER
FLOW (L/S)
AIR ON
CONDENSER (°C)
MIN MAX MIN MAX MIN MAX
0019EE 4.4 12.8 0.6 9.5 -17.7 51.7
0022EE 4.4 12.8 0.6 9.5 -17.7 51.7
0028EE 4.4 12.8 0.6 9.5 -17.7 51.7
0033EE 4.4 12.8 0.6 9.5 -17.7 51.7
0043EE 4.4 12.8 2.5 12.6 -17.7 51.7
0046EE 4.4 12.8 2.5 12.6 -17.7 51.7
0052EE 4.4 12.8 3.8 18.9 -17.7 51.7
0056EE 4.4 12.8 3.8 18.9 -17.7 51.7
0066EE 4.4 12.8 3.8 18.9 -17.7 51.7