YORK INTERNATIONAL
21
FORM 150.62-NM7 (103)
ELECTRICAL DATA
1
SINGLE-POINT POWER SUPPLY CONNECTIONS – YCAL0043E_ - YCAL0253E_
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Discon-
nect Switch (optional) or Circuit Breaker (optional).)
SYSTEM #1 COMPRESSOR & FAN SYSTEM #2 FIELD SUPPLIED WIRING
COMPR. #1 COMPR. #2 COMPR. #3 FANS COMPR. #1 COMPR. #2 COMPR. #3 FANS
RLA LRA RLA LRA RLA LRA QTY
FLA
(EA)
RLA LRA RLA LRA RLA LRA QTY
FLA
(EA)
12.0 99 12.0 99 — — 2 4.0 ————————
16.6 127 16.6 127 — — 2 4.0 ————————
19.9 167 19.9 167 — — 2 4.0 ————————
23.9 198 23.9 198 — — 2 4.0 ————————
19.9 167 19.9 167 19.9 167 2 4.0 ————————
16.6 127 16.6 127 — — 2 4.0 16.6 127 16.6 127 — — 2 4.0
19.9 167 19.9 167 — — 2 4.0 16.6 127 16.6 127 — — 2 4.0
19.9 167 19.9 167 — — 2 4.0 19.9 167 19.9 167 — — 2 4.0
23.9 198 23.9 198 — — 2 4.0 19.9 167 19.9 167 — — 2 4.0
23.9 198 23.9 198 — — 2 4.0 23.9 198 23.9 198 — — 2 4.0
19.9 167 19.9 167 19.9 167 2 4.0 16.6 127 16.6 127 16.6 127 2 4.0
19.9 167 19.9 167 19.9 167 2 4.0 19.9 167 19.9 167 19.9 167 2 4.0
23.9 198 23.9 198 23.9 198 2 4.0 19.9 167 19.9 167 19.9 167 2 4.0
23.9 198 23.9 198 23.9 198 2 4.0 23.9 198 23.9 198 23.9 198 2 4.0