YORK INTERNATIONAL
22
FORM 150.62-NM7 (103)
ELECTRICAL DATA – SINGLE POINT POWER SUPPLY CONNECTIONS – YCAL0043E_ - YCAL0107E_
DUAL POINT POWER SUPPLY CONNECTIONS – YCAL0117E_ - YCAL0253E
See Notes and Legend on page 19.
TABLE 3 – DUAL POINT POWER SUPPLY CONNECTIONS
(One ore Two Field Provided Power Supply Circuits to the chiller. Field connections to Factory Provided Terminal Blocks per system)
Installation
MODEL
YCAL
VOLT HZ
SYSTEM #1 FIELD SUPPLIED WIRING SYSTEM #1 COMPRESSOR & FAN
MCA
1
MIN N/F
DISC
SW
2
D.E. FUSE CKT. BKR.
5
INCOMING
(LUGS) WIRE
RANGE
6
COMPR. #1 COMPR. #2 COMPR. #3 FANS
MIN
3
MAX
4
MIN MAX RLA LRA RLA LRA RLA LRA QTY
FLA
(EA)
0043
380/415 50 35 60 40 45 40 45 # 10 - # 1 12.0 99 12.0 99 — — 2 4.0
0057
380/415 50 46 60 50 60 50 60 # 10 - # 1 16.6 127 16.6 127 — — 2 4.0
0073
380/415 50 53 60 60 70 60 70 # 10 - # 1 19.9 167 19.9 167 — — 2 4.0
0087
380/415 50 62 100 70 80 70 80 # 10 - # 1 23.9 198 23.9 198 — — 2 4.0
0107
380/415 50 73 100 80 90 80 90 # 10 - # 1 19.9 167 19.9 167 19.9 167 2 4.0
0117
380/415 50 46 60 50 60 50 60 # 10 - # 1 16.6 127 16.6 127 — — 2 4.0
0133
380/415 50 53 60 60 70 60 70 # 10 - # 1 19.9 167 19.9 167 — — 2 4.0
0147
380/415 50 53 60 60 70 60 70 # 10 - # 1 19.9 167 19.9 167 — — 2 4.0
0157
380/415 50 62 100 70 80 70 80 # 10 - # 1 23.9 198 23.9 198 — — 2 4.0
0173
380/415 50 62 100 70 80 70 80 # 10 - # 1 23.9 198 23.9 198 — — 2 4.0
0197
380/415 50 73 100 80 90 80 90 # 10 - # 1 19.9 167 19.9 167 19.9 167 2 4.0
0217
380/415 50 73 100 80 90 80 90 # 10 - # 1 19.9 167 19.9 167 19.9 167 2 4.0
0237
380/415 50 86 100 100 100 100 100 # 10 - # 1 23.9 198 23.9 198 23.9 198 2 4.0
0253
380/415 50 86 100 100 100 100 100 # 10 - # 1 23.9 198 23.9 198 23.9 198 2 4.0