INSTALLATION, OPERATION & MAINTENANCE
AIR-COOLED SCREW LIQUID CHILLERS
Supersedes: 201.18-NM1 (1298)
Form 201.18-NM1 (102)
YCAS AIR-COOLED SCREW LIQUID CHILLERS
YCAS0130 through YCAS0230
YCAS 2 SYSTEM EPROM 031-01798-001 (STANDARD, BRINE & METRIC MODELS COMBINED)
28971AR

Table of Contents

Questions and Answers

  • J
    Jamie ReynoldsAug 6, 2025
    How to troubleshoot a York YCAS0210 Chiller with no display on the panel and that won't start?
    • T
      Tracy HenryAug 6, 2025
      If there is no display on the control panel and the York Chiller won't start, here's what you can check: * Ensure the main power supply to the control system is switched on. * Verify that the emergency stop switch on the control panel and any remote emergency stop devices are in the ON position. * Inspect the mains supply in case of an undervoltage relay trip. * Check the emergency stop switch fuses, wiring from - T2 to powerboard and fuse if there's no supply to - T2 or no 24VAC supply to the powerboard. * If there's no +12V output from the powerboard, consider replacing the powerboard or reducing excessive load on the board.
  • R
    Ronald HopkinsAug 10, 2025
    What to do if my York YCAS0210 Chiller displays a HIGH AMBIENT TEMP fault?
    • T
      Tracy SchwartzAug 10, 2025
      If your York Chiller displays a 'HIGH AMBIENT TEMP' fault, it means the ambient air temperature is exceeding the programmed operating limit. Use the 'ambient temp.' key to check the temperature reading. If the reading is accurate, the message should disappear once the ambient temperature drops below the limit. Also, verify that the programmed settings are correct for the unit's options. Check that the fan is operating correctly and the rotation is correct. Check for airflow recirculation. Finally, check the sensor calibration, location, and wiring to ensure accurate temperature measurement.
  • R
    Ronald HorneAug 14, 2025
    How do I fix a HIGH OIL TEMP error on my York Chiller?
    • C
      Christopher DaughertyAug 14, 2025
      If the York Chiller displays a 'HIGH OIL TEMP' message, it could be due to poor airflow through the condenser coils. Check for any obstructions blocking the intake faces of the air coils. Also, verify the accuracy of the temperature reading by checking the sensor calibration, location, and wiring.
  • M
    matthew42Aug 19, 2025
    Why does my York YCAS0210 display 'NO RUN PERM'?
    • H
      hcalderonAug 19, 2025
      If the York Chiller displays 'NO RUN PERM', it indicates a 'No run permissive' status. This can happen if there's no liquid flow through the cooler. Ensure that liquid pumps are running, valves are correctly set, and flow is established. Also, check that the flow switch is functional and correctly installed per the manufacturer's instructions, as the pump starter might be wired to and controlled by the unit on some systems.
  • H
    Heather LutzAug 22, 2025
    What causes a LOW WATER TEMP fault on a York YCAS0210?
    • C
      Chad AtkinsonAug 23, 2025
      If the York Chiller displays a 'LOW WATER TEMP' fault, it could be due to several reasons. The leaving liquid temperature might be dropping below the programmed low limit faster than the unit can unload. Check for any restrictions in the liquid flow line and ensure stable liquid flow. Also, verify the unit is unloading correctly by checking the supply to the unloader valve solenoid and confirming the compressor unloads correctly. Finally, ensure the temperature readings are accurate by checking the sensor calibration, location, and wiring.
  • D
    Donna WilliamsAug 27, 2025
    What does LOW AMBIENT TEMP mean on my York YCAS0210 Chiller?
    • N
      Nicholas EdwardsAug 27, 2025
      If your York Chiller displays a 'LOW AMBIENT TEMP' fault, it means the ambient air temperature is below the programmed operating limit. Use the 'ambient temp.' key to display the temperature and confirm its accuracy. The warning should clear once the ambient temperature rises above the limit. Also, ensure the programmed settings are correct for the unit's options, and check the sensor calibration, location, and wiring.
  • C
    Christopher WashingtonAug 31, 2025
    What causes VAC UNDERVOLTAGE fault on a York YCAS0210?
    • B
      Brandon WalkerAug 31, 2025
      If the York Chiller displays 'VAC UNDERVOLTAGE', it indicates a problem with the mains supply voltage. Check that the mains supply is stable and within allowable limits. Also, check for any voltage dips when the compressor starts.

York YCAS0210 Specifications

General IconGeneral
ModelYCAS0210
RefrigerantR-134a
Phase3
Frequency60 Hz
Cooling Capacity210 Tons
Voltage460V
Height96 in (2438 mm)