41YORK INTERNATIONAL
FORM 201.18-NM1 (102)
Pressure Drop (kPa)
6 8 9 11 13 16 19 22 25 28
Flow Rate (l/s)
3
6
9
12
15
30
45
60
75
90
105
120
134
149
31 35 38 41 44 47 50
A
B
Pressure Drop (FT - H
2
O)
100 125 150 175 200 250 300 350 400 450
Flow Rate (GPM)
1
2
3
4
5
10
15
20
25
30
35
40
45
50
500
550
600
650
700
750
800
A
B
ETHYLENE GLYCOL
PROPYLENE GLYCOL
A
A
B
B
C
C
1.45
1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1.0
-10-8-6-4-20 2468
-10 -8 -6 -4 -2 0 2 4 6 8
50%
40%
30%
20%
10%
50%
40%
30%
20%
10%
˚C
˚C
TECHNICAL DATA
GLYCOL CORRECTION FACTORS
The cooler is designed in accordance with ARI-590-92
which allows for an increase in pressure drop of up to
15% above the design value given above. Debris in the
water may also cause additional pressure drop.
When using glycol solutions, pressure drops are higher
than with water (see correction factors to be applied
when using glycol solutions). Special care must be taken
not to exceed the maximum allowed.
A = Correction Factor
B = Mean Temperature through Cooler
C = Concentration W/W
COOLER WATER PRESSURE DROP
(ENGLISH UNITS)
LD03504
COOLER WATER PRESSURE DROP
(SI UNITS)
FIG. 14 – FLOW RATE AND PRESSURE DROP CHARTS
FIG. 15 – GLYCOL CORRECTION FACTORS
FLOW RATE AND PRESSURE DROP CHARTS
LD03503
Excessive flow, above the max GPM,
will damage the evaporator.
LD03503m
7
MODEL NUMBER YCAS COOLER
0130 - 0140 A
0150 - 0230 B