EasyManua.ls Logo

York YCAS0250 - Optional Single-Point Power Supply Connection with Individual Unit Circuit Breakers; 3 & 4 Compressor Units

York YCAS0250
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
YORK INTERNATIONAL
10
FORM 201.19-W2 (304)
ELECTRICAL DATA (CONT'D)
OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION
AND INDIVIDUAL SYSTEM CIRCUIT BREAKERS
One eld provided power sup ply cir cuits to the unit with
in di vid u al branch cir cuit protection. Field Power Wiring
connections to fac to ry provided, Non-Fused Dis con nect
Switches (Opt), or Ter mi nal Blocks (Opt) in the Option
Box.
Suitable for:
Y - Start and
Across-The-Line-Start
LD05548
See page 6 for notes.
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION WITH INDIVIDUAL UNIT CIRCUIT BREAKERS
3 & 4 COMPRESSOR UNITS
(One Field Provided Power Supply Circuit to the chiller. Field connections to Power Terminal Block (standard) or Non-Fused Disconnect (option)
in ‘Option Panel’. Circuit Breakers in each Motor Control Center
FIELD SUPPLIED WIRING
CHILLER
FIELD PROVIDED POWER SUPPLY FACTORY PROVIDED (LUGS) WIRE RANGE
7
MODEL
YCAS
VOLTS
MCA
1
MIN NF OVER-CURRENT PROTECTION
13
TERMINAL BLOCK NF DISC. SWITCH
DISC SW
2, 9
MIN.
3, 5
MAX.
4, 6
(LUGS) WIRE RANGE (LUGS) WIRE RANGE
380 561 600 600 700 (2) 2/0-500 (2) 250-500
0250EC 460 464 600 500 500 (2) 1/0-300 (2) 250-500
575 372 400 400 450 (2) # 2-4/0 (3) 2/0-250
380 651 800 800 800 (2) 2/0-500 (3) 2/0-400
0270EC 460 534 600 600 700 (2) 2/0-500 (2) 250-500
575 427 600 500 500 (2) 1/0-300 (2) 250-500
380 678 800 800 800 (3) 1/0-300 (3) 2/0-400
0300EC 460 559 600 600 700 (2) 2/0-500 (2) 250-500
575 445 600 500 500 (2) 1/0-500 (2) 250-500
380 745 800 800 800 (3) 1/0-300 (3) 2/0-400
0330EC 460 612 800 700 700 (2) 2/0-500 (3) 2/0-400
575 487 600 600 600 (2) 1/0-300 (2) 250-500
380 835 1000 1000 1000 (3) 2/0-500 (4) 4/0-500
0360EC 460 689 800 800 800 (3) 1/0-300 (3) 2/0-400
575 550 600 600 600 (2) 2/0-500 (2) 250-500
380 896 1000 1000 1000 (3) 2/0-500 (4) 4/0-500
0400EC 460 739 1000 800 800 (3) 2/0-500 (4) 4/0-500
575 589 800 700 700 (2) 2/0-500 (3) 2/0-400
380 991 1200 1200 1200 (3) 2/0-500 (4) 4/0-500
0440EC 460 812 1000 1000 1000 (3) 2/0-500 (4) 4/0-500
575 647 800 800 800 (2) 2/0-500 (3 )2/0-400
CB
3
CB
4
CB
1
CB
2
TB
or
DS
F
ield Supply
Suitable for:
Y - D Start and
Across the Line Start
See Note 3

Table of Contents

Related product manuals