10
Units without pack
(1) Weight for unit empty. (2) Available static pressure, Eurovent certified. (3) Pressure with clean filter. (4) Weight with dual pump.
Sound power spectrum
Standard units
Units with hydro kit (version P)
Low noise level units
The data appearing in the tables are sound power values in compliance with the ISO EN 3743 standard.
No. of pumps 1
Available static pressure at rated flow
(without filter) for cooling mode (2)
kPa 231 205
Available static pressure at rated flow
(with filter) for cooling mode (3)
kPa 228 200
Pump consumption W 3 180 3 400
Pump amperage A 5.5 6.1
Unit water content l 18 (T) / 170 (TP) 22.5 (T) / 179 (TP)
Expansion vessel volume l 25 35
Relief valve setting Bar 6
Max. unit power consumption kW 58.3 74.5
Max. unit current amperage A 108 120
Start-up amperage (compressor) A 118 198
Weight (1) / (4) kg 1 280 / 1 316 1 675 / 1 703
Start-up amperage (compressor) A 118 198
Pressure drop kPa 29.5 25.5
Max. unit power consumption kW 53 71.1
Max. current amperage A 103 114
Weight (1) kg 1 220 1 615
Models
Hz
125 250 500 1 000 2 000 4 000 8 000 dB(A)
YCSA/YCSA-H 120
78 80 81 79 75 68 63 86
YCSA/YCSA-H 150
79 83 84 80 77 69 64 88
Models
Hz
125 250 500 1 000 2 000 4 000 8 000 dB(A)
YCSA/YCSA-H 120
75 76 77 73 59 58 53 82
YCSA/YCSA-H 150
76 78 79 73 68 59 54 84