37
-A- Antifreeze
-C- Compressor configuration
DESCRIPCIÓN RANGE UNIT VALUE
Antifreeze alarm set point -99.9/99.9 °C 3
Antifreeze alarm dif. set point 99.9 °K 5
Antifreeze alarm set point, lower limit -99.9/99.9 °C 3
Antifreeze alarm set point, upper limit -99.9/99.9 °C 5
Antifreeze alarm reset
MANUAL
AUTOMATIC
- MANUAL
Antifreeze alarm delay (if auto. reset is selected) 0/540 min. 0
Activation set point, antifreeze heater -99.9/99.9 °C 3
Activation dif. set point, antifreeze heater -99.9/99.9 °K 2
Backup heater set point (winter cycle) -99.9/99.9 °C 25
Backup heater dif. set point (winter cycle) -99.9/99.9 °K 5
Backup heater activation delay 0/60 min. 15
Automatic activation of antifreeze system with the unit OFF
DISABLED
HEATER & PUMP
HEATER & UNIT
HEATER
- HEATER
DESCRIPTION RANGE UNIT VALUE
Min. compressor ON time 0/9999 sec. 120
Min. compressor OFF time 0/9999 sec. 60
Time between starts of different compressors 0/9999 sec. 3
Time between starts of one compressor 0/9999 sec. 300
Time between starts of pump and compressor 0/999 sec. 20
Time between compressor and pump OFF 0/999 sec. 20
Run hours, pump 1
Run hours, pump 2
Run hours, compressor 1
Run hours, compressor 2
Run hours, compressor 3
Run hours, compressor 4
Run hours for pump maintenance warning 1000/999000 hours 2x1000
Clear pump run hours
Operating hours for maintenance warning of compressor 1 / circuit 1 1000/999000 hours 2x1000
Clearing of operating hours of compressor 1 / circuit 1
Operating hours for maintenance warning of compressor 2 / circuit 1 1000/999000 hours 2x1000
Clearing of operating hours of compressor 2 / circuit 1
Operating hours for maintenance warning of compressor 1 / circuit 2 1000/999000 hours 2x1000
Clearing of operating hours of compressor 1 / circuit 2
Operating hours for maintenance warning of compressor 2 / circuit 2 1000/999000 hours 2x1000
Clearing of operating hours of compressor 2 / circuit 2
Rotational time of tandem compressors min. 20
Enable compressors C
1
/
1
, C
2
/
1
, C
1
/
2
and C
2
/
2
Y/N Y
Forced manual operation of compressors Y/N N