39
-H- Unit configuration
DESCRIPTION RANGE UNIT VALUE
Unit type 0 - 7 -
2 (CHILLER)
3 (HP)
Number of compressors / circuits - 4 / 2
Rotation of compressors
LIFO
FIFO
TIME
CUSTOM
-
FIFO
Number of evaporators 1 - 2 - 1
Driver number (EVD400) 0-1-2-4 - 0
Cycle inverting valve logic NO/NC - NC
Number of pumps 1 - 2 -
1 (SINGLE)
2 (DUAL PUMP
ACCESSORY)
Pump operation
ON WITH COMP. ON
ALWAYS OFF
ALWAYS ON
SAFETY ON/ OFF
ALWAYS ON
Rotation of pumps
START TIME
-
TIME
Number of hours for pump rotation 0-9999 hours 12
Enable ON/OFF digital input Y/N - NO
Enable WINTER/SUMMER digital input Y/N - NO
Enable ON/OFF with Monitor Y/N - NO
Enable WINTER/SUMMER with Monitor Y/N - NO
Inversion delay SUMMER/WINTER operation sec 10
Monitor protocol
CAREL
MODEM GSM
ANALOGUE MODEM
RS 232
LONWORKS
MODBUS
-
CAREL
Communication speed sel.
1200; 2400; 4800;
9600; 19200
bauds 19200
ID number for Monitor 0-200 - 1
Enable language selection at commissioning Y/N - Y
Restore default values (Attention!) Y/N - N