Model YORK
Unit YHKJZH060BARXAFX
Outdoor YHUJYH060BASXA-X
Indoor YHKMXH060BARX-FX
Power supply V/Ph/Hz 400/3/50(60)
Rated Cooling
Capacity Btu/h 49272
Capacity kW(min~max) 14.4(3.7~15.1)
Input W(min~max) 5124(2000~6500)
Rated current A 8.5
EER W/W 2.81
SEER W/W /
Cooling P design
Rated Heating
Capacity Btu/h 52507
Capacity kW(min~max) 15.4(3.7~16.0)
Input W(min~max) 5110(2000~6500)
Rated current A 8.5
COP W/W 3.01
SCOP W/W /
Heating P design(-10
O
C) kW /
Moisture Removal l/h 5.0
Max. input consumption W 6500
Max. current A 10.5
Starting current A 3
Operation Control Wired&Wireless
Indoor coil
Number of row 2
Fin spacing mm 1.3
Fin material Hydrophilic Aluminium
Tube outside diameter mm 7
Tube material Inner Grooved copper tube
Coil length x height x width mm 2775x26.6x210
Number of circuit 10
Indoor fan motor
Model KFD-60G-1
Input W 190
Output W 60
Running current A 1.2
Capacitor uF 4.5
Speed (Hi/Me/Lo) rpm 670/550/460
Indoor air ow at 0/50/100 Pa(Hi/Me/Lo) m3/h 1980/1750/1500
External static pressure Pa /
Indoor noise level(Sound power level) (Hi/Me/Lo) dB(A) /
Indoor noise level (Sound pressure level)(Hi/Me/Lo) dB(A) 49/44/42
Indoor dimension
Unit (WxDxH) mm 1230×840×280
Packing (WxDxH) mm 1325×920×370
Indoor weight
Net kg 38.6
Gross kg 45.7
Panel dimension
Unit (WxDxH) mm
1340×950×80
Packing (WxDxH) mm
1400×995×115
Panel weight
Net kg
8.4
Gross kg
12.7
Outdoor coil
Number of row
2
Fin spacing mm
1.5
Fin material
Hydrophilic Aluminium
Tube outside diameter mm 7.94
Tube material Inner Grooved copper tube
Coil length x height x width mm
970x38.1x1200
Number of circuit
10
19

Related product manuals