JOHNSON CONTROLS
36
FORM 160.76-O1
ISSUE DATE: 6/15/2015
SECTION 7 - PREVENTIVE MAINTENANCE
Procedure Daily Weekly Monthly Yearly Other
Record operating conditions (on applicable Log Form) X
Check oil levels X
Check refrigerant levels X
Check oil return system operation X
Check operation of motor starter X
Check sump heater and thermostat operation X
Check three-phase voltage and current balance X
Verify proper operation/setting/calibration of safety controls
1
X
Verify condenser and evaporator water ows X
Leak check and repair leaks as needed
1
X
Check and tighten all electrical connections X
Megohm motor windings X
Replace oil lter and oil return lter/driers X
Clean or backush heat exchanger (VSD, SSS Applications) X
Replace starter coolant (VSD, SSS Applications) X
Replace or clean starter air lters if applicable X
2
Perform oil analysis on compressor lube oil
1
X
Perform refrigeration analysis
1
X
Perform vibration analysis X
Clean tubes X
2
Perform Eddy current testing and inspect tubes 2-5 Years
Lubricate motor Refer to motor manufacturer’s recommendations
For operating and maintenance requirements listed above, refer to appropriate service literature, or contact your local Johnson Controls Service Ofce. A record of all procedures being successfully car-
ried out (as well as operating logs) must be maintained on le by the equipment owner should proof of adequate maintenance be required at a later date for warranty validation purposes.
1
This procedure must be performed at the specied time interval by an Industry Certied Technician who has been trained and qualied to work on this type of YORK equipment.
2
More frequent service may be required depending on local operating conditions.
MAINTENANCE REQUIREMENTS FOR YORK YK CHILLERS
160.54-MR1 (611)
Supersedes 160.54-MR1 (801)
Issue Date: June 20, 2011