SECTION 2 – PRODUCT DESCRIPTION
FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
2
Number of compressors
Low liquid temperature cutout
Low suction pressure cutout
High discharge pressure cutout
Anti-recycle timer (compressor start cycle time)
Anti-coincident timer (delay compressor starts)
Unit Keys
This section is used to:
Set time
Set unit options
Oper Data Key
The microprocessor control center is capable of dis-
playing the following:
Return and leaving liquid temperature
Low leaving liquid temperature cutout setting
Low ambient temperature cutout setting
Outdoor air temperature
English or Metric data
Suction pressure cutout setting
Each system suction pressure
Discharge pressure (optional)
Liquid Temperature Reset via a Johnson Controls
ISN DDC or Building Automation System (by
others) via a 4 to 20 milliamp or 0 to 10VDC input
Anti-recycle timer status for each system
Anti-coincident system start timer condition
Compressor run status
No cooling load condition
Day, date and time
Daily start/stop times
Holiday status
Automatic or manual system lead/lag control
Lead system denition
Compressor starts and operating hours
(each compressor)
Status of hot gas valves, evaporator heater
and fan operation
Run permissive status
Number of compressors running
Liquid solenoid valve status
Load and unload timer status
Water pump status
Provisions are included for: pumpdown at shutdown;
optional remote chilled water temperature reset and
two steps of demand load limiting from an external
building automation system. Unit alarm contacts are
standard.
The operating program is stored in non-volatile memo-
ry battery backed RAM to eliminate chiller failure due
to AC powered failure/battery discharge. Programmed
setpoints are retained in lithium battery-backed RTC
memory for 5 years minimum.
COMMUNICATIONS
Native communication capability for BACnet
(MS/TP) and Modbus.
Optional communication available for N2 and
LON via eLink Gateway option.
BUILDING AUTOMATION SYSTEM
INTERFACE
The Microprocessor Board can accept a 4 to 20 milli-
amp, or 0 to 10VDC input to reset the leaving chiller
liquid temperature from a Building Automation Sys-
tem.
The standard unit capabilities include remote
start-stop, remote water temperature reset via a
PWM 4 to 20 milliamp or 0 to 10VDC input sig-
nal or up to two stages of demand (load) limiting
depending on model.
The standard control panel can be directly con-
nected to a Johnson Controls Building Automated
System.
POWER PANEL
Each panel contains:
Compressor power terminals
Compressor motor starting contactors per I.E.C.**
Control power terminals to accept incoming for
115-1-60 control power
Fan contactors and overload current protection
The power wiring is routed through liquid-tight con-
duit to the compressors and fans.